Voltage Drop Calculator (Drop %, Volts & Max Length by Wire Size)

Calculate voltage drop instantly.

Inputs

Solve For
Load Entered As
A
V

ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).

ℹ️Not sure what size you have (or need)? Use the Wire Size Calculator instead — this tool checks a specific size you already have in mind.

ℹ️Distance from the panel/breaker to the load, one way — not round trip.

ℹ️The threshold your result is checked against.

Cost

Enable Cost Estimation?

Voltage Drop: 3.29% (3.95 V)

Exceeds your 3.0% allowed limit

Circuit Details

Wire size12 AWG (Copper)
Load current20.0 A
System120 V, single-phase
One-way run length50.0 ft (15.2 m)
Receiving-end voltage116.1 V
Ampacity sanity check (75°C, no derating)Looks adequate (25 A base)

Compare Across Wire Sizes

AWGDrop %Result
14 AWG5.23%Fail
12 AWG (selected)3.29%Fail
10 AWG2.07%Pass
8 AWG1.30%Pass
6 AWG0.82%Pass
4 AWG0.52%Pass
3 AWG0.41%Pass
2 AWG0.32%Pass
1 AWG0.26%Pass
1/0 AWG0.20%Pass
2/0 AWG0.16%Pass
3/0 AWG0.13%Pass
4/0 AWG0.10%Pass

Row highlighted in blue is your selected wire size. "Pass"/"Fail" is against your 3.0% allowed drop only — always confirm ampacity separately with the Wire Size Calculator.

Assumptions Used

Voltage drop uses K = 12.9 (copper) / 21.2 (aluminum) ohm-cmil/ft — the same formula and constants as the Wire Size Calculator, so results stay consistent between the two tools. The ampacity sanity check is informational only (base 75°C table, no derating) — use the Wire Size Calculator for a full ampacity and breaker sizing check.

Need to find the right wire size from scratch instead of checking one? Wire Size Calculator →

Voltage Drop VisualizationSource120 VLoad116.1 V3.29% dropLength: 50.0 ftDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Voltage Drop Calculator.

General voltage drop estimate

This page gives the full combined voltage-drop result — drop volts, drop percent, receiving-end voltage, pass/fail, and a full comparison across every standard wire size — from one set of wire, load, and length inputs.

It's the same calculator behind every other voltage drop variant on this site, just without a specific scenario pre-selected — useful for a general check before finalizing the exact circuit.

  • Checks a wire size you already have in mind, rather than recommending one.
  • Solve in either direction — voltage drop for a given length, or maximum length for a target drop.
  • Comparison table shows every standard AWG size side by side.

Voltage Drop Formula: How Is It Calculated?

The same underlying resistance-based formula runs in both directions — solving for drop given a length, or solving for the maximum length given a target drop percentage.

Step 1 — Voltage Drop (given length)

Voltage Drop (V) = (2 × K × I × D) / CM [single-phase]

Voltage Drop (V) = (1.732 × K × I × D) / CM [three-phase]

Drop % = (Voltage Drop ÷ System Voltage) × 100

K is a resistivity constant (12.9 for copper, 21.2 for aluminum, ohm-circular-mil/ft), I is the load current, D is the one-way run length in feet, and CM is the selected wire size's circular-mil area. This is the same formula and constants used by the Wire Size Calculator, so both tools always agree on the same inputs.

Step 2 — Maximum Length (given target drop %)

Allowed Voltage Drop (V) = System Voltage × Max Drop % ÷ 100

Maximum Length (ft) = (Allowed Voltage Drop × CM) ÷ (2 × K × I) [single-phase, 1.732 for three-phase]

This is the same formula solved for distance instead of voltage — useful when the question is "how far can this wire go?" rather than "what's the drop at this length?"

Step 3 — Receiving-End Voltage & Pass/Fail

Receiving Voltage = System Voltage − Voltage Drop

Passes = Drop % ≤ Max Allowed %

The result is checked against your selected maximum (commonly 3% for a single branch circuit or feeder, per NEC's recommendation) and flagged as passing or failing that threshold.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Wire size / material12 AWG, copperSets circular-mil area and resistivity constant K
Load current / voltage20.0 A, 120 V, single-phaseSets current and the drop-percent base
Solve for / max dropVoltage drop, 3.0% maxSets which formula direction runs and the pass/fail threshold

Step 1 — Voltage Drop

CalculationResult
Voltage drop at 50.0 ft3.95 V (3.29%)
Receiving-end voltage116.1 V (fails the 3.0% limit)

Therefore, 12 AWG copper carrying 20.0A at 120V over 50.0 ft has a 3.29% drop, which fails your 3.0% limit.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

No — this checks a specific size you provide. Use the Wire Size Calculator if you want a size recommended from your load.
Yes — set Solve For to "Max Length" and the calculator solves the same formula for distance instead of voltage.