3% Voltage Drop Calculator (NEC Branch Circuit Limit)

Check against the 3% NEC limit.

Inputs

Solve For
Load Entered As
A
V

ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).

ℹ️Not sure what size you have (or need)? Use the Wire Size Calculator instead — this tool checks a specific size you already have in mind.

ℹ️Distance from the panel/breaker to the load, one way — not round trip.

ℹ️The threshold your result is checked against.

Cost

Enable Cost Estimation?

Voltage Drop: 3.29% (3.95 V)

Exceeds your 3.0% allowed limit

Circuit Details

Wire size12 AWG (Copper)
Load current20.0 A
System120 V, single-phase
One-way run length50.0 ft (15.2 m)
Receiving-end voltage116.1 V
Ampacity sanity check (75°C, no derating)Looks adequate (25 A base)

Compare Across Wire Sizes

AWGDrop %Result
14 AWG5.23%Fail
12 AWG (selected)3.29%Fail
10 AWG2.07%Pass
8 AWG1.30%Pass
6 AWG0.82%Pass
4 AWG0.52%Pass
3 AWG0.41%Pass
2 AWG0.32%Pass
1 AWG0.26%Pass
1/0 AWG0.20%Pass
2/0 AWG0.16%Pass
3/0 AWG0.13%Pass
4/0 AWG0.10%Pass

Row highlighted in blue is your selected wire size. "Pass"/"Fail" is against your 3.0% allowed drop only — always confirm ampacity separately with the Wire Size Calculator.

Assumptions Used

Voltage drop uses K = 12.9 (copper) / 21.2 (aluminum) ohm-cmil/ft — the same formula and constants as the Wire Size Calculator, so results stay consistent between the two tools. The ampacity sanity check is informational only (base 75°C table, no derating) — use the Wire Size Calculator for a full ampacity and breaker sizing check.

Need to find the right wire size from scratch instead of checking one? Wire Size Calculator →

Voltage Drop VisualizationSource120 VLoad116.1 V3.29% dropLength: 50.0 ftDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Voltage Drop Calculator.

3% voltage drop check

3% is the NEC-recommended maximum voltage drop for a single branch circuit or feeder considered on its own — this page is pre-set to that threshold.

Edit the wire size, load, or length above and the pass/fail result updates against the 3% limit.

  • 3% applies to a single branch circuit or feeder segment, not the combined path.
  • 5% is the separate combined limit for a feeder plus its branch circuits together — use the Max Voltage Drop Allowed dropdown to switch.
  • A failing result here means either upsizing the wire or shortening the run.

Voltage Drop Formula: How Is It Calculated?

The same underlying resistance-based formula runs in both directions — solving for drop given a length, or solving for the maximum length given a target drop percentage.

Step 1 — Voltage Drop (given length)

Voltage Drop (V) = (2 × K × I × D) / CM [single-phase]

Voltage Drop (V) = (1.732 × K × I × D) / CM [three-phase]

Drop % = (Voltage Drop ÷ System Voltage) × 100

K is a resistivity constant (12.9 for copper, 21.2 for aluminum, ohm-circular-mil/ft), I is the load current, D is the one-way run length in feet, and CM is the selected wire size's circular-mil area. This is the same formula and constants used by the Wire Size Calculator, so both tools always agree on the same inputs.

Step 2 — Maximum Length (given target drop %)

Allowed Voltage Drop (V) = System Voltage × Max Drop % ÷ 100

Maximum Length (ft) = (Allowed Voltage Drop × CM) ÷ (2 × K × I) [single-phase, 1.732 for three-phase]

This is the same formula solved for distance instead of voltage — useful when the question is "how far can this wire go?" rather than "what's the drop at this length?"

Step 3 — Receiving-End Voltage & Pass/Fail

Receiving Voltage = System Voltage − Voltage Drop

Passes = Drop % ≤ Max Allowed %

The result is checked against your selected maximum (commonly 3% for a single branch circuit or feeder, per NEC's recommendation) and flagged as passing or failing that threshold.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Wire size / material12 AWG, copperSets circular-mil area and resistivity constant K
Load current / voltage20.0 A, 120 V, single-phaseSets current and the drop-percent base
Solve for / max dropVoltage drop, 3.0% maxSets which formula direction runs and the pass/fail threshold

Step 1 — Voltage Drop

CalculationResult
Voltage drop at 50.0 ft3.95 V (3.29%)
Receiving-end voltage116.1 V (fails the 3.0% limit)

Therefore, 12 AWG copper carrying 20.0A at 120V over 50.0 ft has a 3.29% drop, which fails your 3.0% limit.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

It's a recommendation in an informational note (FPN), not a strict numeric code requirement in most jurisdictions — but it's the widely accepted design target for a single branch circuit or feeder, and many designers and inspectors treat it as the practical limit.
Use the 5% combined limit instead — switch the Max Voltage Drop Allowed dropdown to 5% for a feeder-plus-branch total, not 3% applied to each segment separately.