Circuit Breaker Size Calculator (NEC 210.20 / 240.6 — Single or Multiple Loads)
Calculate breaker size instantly.
🕒 Last updated: August 27, 2026
Inputs
ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).
ℹ️Determines pole count — voltage alone doesn't tell you this. 120V and 277V circuits are typically line-to-neutral (1-pole); 240V split-phase and 208V are typically line-to-line (2-pole).
ℹ️Flags GFCI (NEC 210.8) and AFCI (NEC 210.12) protection requirements for dwelling units — always confirm against local code amendments.
Wire Cross-Check
Cost
Recommended Breaker: 20A (1-pole)
From 16.0A design current at 120V, single-phase
Protection Required — General / Other (living area, hallway, closet)
• AFCI protection required (NEC 210.12(A))
Circuit Summary
Design current basis: NEC 210.20(A) — 100% non-continuous + 125% continuous
Standard size: NEC 240.6(A)
Poles: 1-pole
Assumptions Used
NEC 210.20(A) continuous-load 125% factor, NEC 240.6(A) standard ampere ratings. GFCI/AFCI flags are a general dwelling-unit planning reference per NEC 210.8/210.12 — always confirm against local code amendments. This is a reference estimate — confirm with a licensed electrician before final installation.
Need to find the right wire size for this breaker from scratch? Wire Size Calculator →
Checking a long run's voltage drop instead? Voltage Drop Calculator →
What Is a Circuit Breaker Size Calculator?
A circuit breaker size calculator recommends the correct standard breaker (overcurrent protective device) rating for a circuit, based on its load current — applying NEC 210.20(A)'s continuous-load 125% safety factor, then rounding up to the nearest NEC 240.6(A) standard ampere rating (15, 20, 25, 30A, and so on).
Unlike the Wire Size Calculator (which starts from a load and finds the right wire, with the breaker as one part of that result), this tool goes straight from load to breaker — and can combine several loads sharing one circuit into a single combined breaker size, which the Wire Size Calculator doesn't do.
Why getting breaker size right matters:
- An undersized breaker trips nuisance-fashion under normal load, or worse, doesn't protect the circuit as intended
- An oversized breaker fails to trip before the wire is damaged — a genuine fire safety risk, not just an inconvenience
- Combining multiple loads onto one circuit without properly summing their design currents is a common source of undersized breakers on shared circuits
- GFCI/AFCI protection requirements vary by circuit location and are easy to overlook when focused only on the amperage question
Circuit Breaker Formula: How Is Size Calculated?
The core calculation is the same whether there's one load or several sharing a circuit — the difference is how the design current is built up before rounding to a standard size.
Step 1 — Design Current per Load
Design Current = Load Current × 1.25 (if continuous — 3+ hours)
Design Current = Load Current (if not continuous)
Per NEC 210.20(A), a continuous load needs a 25% safety margin; a non-continuous load uses its actual current directly. This is applied per load before combining multiple loads onto one circuit.
Step 2 — Combined Design Current (Multiple Loads)
Total Design Current = Sum of every load's own Design Current
When several loads share one circuit, sum each load's own design current (not the raw currents first, then apply 125% once) — mathematically identical to NEC's own phrasing of noncontinuous-sum plus 125% of continuous-sum, since multiplication distributes over the sum.
Step 3 — Standard Breaker Size
Recommended Breaker = smallest NEC 240.6(A) standard rating ≥ Total Design Current
Standard ampere ratings (15, 20, 25, 30, 35, 40, 45, 50, 60A, and larger) come from NEC 240.6(A) — a breaker is always sized up to the next standard rating, never to a custom in-between value.
Worked Example
This example walks through your current inputs above, using the same steps as the Formula section.
Input Values Used
| Input | Value | Why it is used |
|---|---|---|
| Load(s) | 16.0 A | Sets the total design current |
| System | 120 V, single-phase | Sets number of poles |
| Location | General / Other (living area, hallway, closet) | Sets GFCI/AFCI requirement flags |
Step 1 — Design Current
| Calculation | Result |
|---|---|
| Total base current | 16.0 A |
| Total design current | 16.0 A |
Therefore, for 16.0A of design current at 120V, you need a 20A, 1-pole breaker, with AFCI protection required for general / other (living area, hallway, closet).
Essential Checklist+−
Complete these critical checks before approving the work or proceeding to the next construction stage.
✓Load Classification+-
- Load current confirmed from equipment nameplate, not estimated
- Continuous vs. non-continuous classification confirmed for every individual load, not applied as one blanket assumption
- Loads entered in Multiple Loads mode genuinely share one physical circuit/breaker
- No informal "diversity" or simultaneous-use reduction applied to a single branch circuit's load
✓Formula Application+-
- 125% continuous-load factor applied per load, then summed — not applied once to a pre-summed raw total
- Final breaker size confirmed as a genuine NEC 240.6(A) standard rating, rounded up
- Single-phase vs. three-phase confirmed against the actual service/panel
✓GFCI/AFCI Protection Requirements+-
- Circuit location selected matches the actual room/area the circuit will serve
- Combination AFCI/GFCI (dual-function) breaker specified where a location requires both protections
- Local code edition and amendments checked for GFCI/AFCI requirements, not assumed from a general reference
✓Wire Cross-Check & Code Compliance+-
- Recommended breaker checked against the actual wire size being installed, not assumed automatically compatible
- Permit and inspection requirements confirmed for the scope of work
- Work beyond a simple single-circuit breaker check reviewed or performed by a licensed electrician
Full QC Checklist+−
Verification checklist for circuit breaker sizing — covering load classification, formula application, GFCI/AFCI protection requirements, and wire/code compliance. Use the Essential Checklist for critical checks before wiring; expand to Full QC Checklist for complete verification.
✓Load Classification+-
- Load current confirmed from equipment nameplate, not estimated
- Continuous vs. non-continuous classification confirmed for every individual load, not applied as one blanket assumption
- Loads entered in Multiple Loads mode genuinely share one physical circuit/breaker
- Power factor entered correctly when sizing from a wattage nameplate rating on a motor or reactive load
- No informal "diversity" or simultaneous-use reduction applied to a single branch circuit's load
✓Formula Application+-
- 125% continuous-load factor applied per load, then summed — not applied once to a pre-summed raw total
- Final breaker size confirmed as a genuine NEC 240.6(A) standard rating, rounded up
- Circuit configuration (line-to-neutral vs. line-to-line) confirmed, not assumed from voltage alone
- Single-phase vs. three-phase confirmed against the actual service/panel
- HACR-rated breaker specified for air conditioning, heat pump, or refrigeration compressor loads
✓GFCI/AFCI Protection Requirements+-
- Circuit location selected matches the actual room/area the circuit will serve
- Method of providing required GFCI protection clarified — breaker-type GFCI vs. GFCI receptacle
- Combination AFCI/GFCI (dual-function) breaker specified where a location requires both protections
- Local code edition and amendments checked for GFCI/AFCI requirements, not assumed from a general reference
- Weatherproof in-use cover confirmed for outdoor or wet-location receptacles, alongside GFCI protection
✓Wire Cross-Check & Code Compliance+-
- Recommended breaker checked against the actual wire size being installed, not assumed automatically compatible
- Breaker's interrupting (AIC) rating confirmed adequate for the available fault current at its location
- An existing installed breaker re-verified against actual current load, not assumed correctly sized because it's already installed
- Permit and inspection requirements confirmed for the scope of work
- Work beyond a simple single-circuit breaker check reviewed or performed by a licensed electrician
NEC 240.6(A) Standard Breaker Sizes
Standard ampere ratings for fuses and inverse time circuit breakers — a breaker rating always rounds up to one of these, never to a custom in-between value.
| Standard Sizes (A) |
|---|
| 15, 20, 25, 30, 35, 40, 45, 50, 60 |
| 70, 80, 90, 100, 110, 125, 150, 175, 200 |
| 225, 250, 300 (this calculator's upper limit) |
NEC 240.6(A) lists further sizes above 300A (350, 400, 450A, and beyond) for larger service and feeder work — outside this calculator's scope.
When should you use this circuit breaker calculator?
- Sizing a breaker for a new single-load branch circuit.
- Combining several loads sharing one panel circuit into one correctly-sized breaker.
- Checking whether an existing breaker is adequate — or oversized — for its actual load.
- Confirming GFCI/AFCI protection requirements for a specific room or location before purchasing a breaker.
- Cross-checking a recommended breaker against a specific wire size already chosen.
Quick Circuit Breaker Sizing Tips
- Classify each load's continuous status carefully — most lighting and HVAC circuits run 3+ hours and need the 125% factor.
- Use Multiple Loads mode for any shared circuit — summing raw currents without each load's own 125% factor understates the requirement.
- Check GFCI/AFCI requirements by the room the circuit actually serves, not just its amperage — this is easy to overlook.
- Always cross-check the recommended breaker against the actual wire size, especially for 14/12/10 AWG conductors capped by NEC 240.4(D).
- Never round a breaker size down to save cost — always round up to the next NEC 240.6(A) standard size.
Common Mistakes
- Forgetting the 125% continuous-load factor, or applying it to non-continuous loads that don't need it.
- Summing multiple loads' raw currents first and applying 125% once to the total, instead of per-load — this understates the requirement whenever the mix of continuous/non-continuous loads differs.
- Sizing the breaker to the load without cross-checking it against the actual wire — a breaker that exceeds the wire's rating defeats the wire's overcurrent protection.
- Assuming GFCI/AFCI requirements only apply to bathrooms — kitchens, garages, outdoor circuits, and most habitable rooms have their own requirements too.
- Rounding a breaker size down to the nearest standard rating instead of up — NEC 240.6(A) sizing always rounds up.
Limitations
- GFCI/AFCI flags are a general dwelling-unit planning reference per NEC 210.8/210.12 — local amendments and edition differences can change specifics; always confirm against the code actually adopted locally.
- The wire cross-check is informational only (small-conductor cap or base 75°C ampacity, no derating) — use the Wire Size Calculator for a full ampacity, derating, and conduit-fill check.
- Covers standard breaker sizes up to 300A — larger service/feeder overcurrent devices are outside this calculator's scope.
- NEC-based only (US) — other regions use different overcurrent protection standards and conventions and this calculator does not model them.
Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.