TryBuildCalc

Kitchen Circuit Breaker Calculator (Countertop Receptacle Circuit Sizing)

Size a kitchen circuit breaker.

Inputs

Multiple Loads on One Circuit?
Load Entered As
A
Continuous Load (3+ hours)?
V

ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).

ℹ️Determines pole count — voltage alone doesn't tell you this. 120V and 277V circuits are typically line-to-neutral (1-pole); 240V split-phase and 208V are typically line-to-line (2-pole).

ℹ️Flags GFCI (NEC 210.8) and AFCI (NEC 210.12) protection requirements for dwelling units — always confirm against local code amendments.

Wire Cross-Check

Cross-Check Against a Specific Wire Size?

Cost

Enable Cost Estimation?

Recommended Breaker: 20A (1-pole)

From 20.0A design current at 120V, single-phase

Protection Required — Kitchen (countertop receptacles)

• GFCI protection required (NEC 210.8)

• AFCI protection required (NEC 210.12(A))

Circuit Summary

Design current basis: NEC 210.20(A) — 100% non-continuous + 125% continuous

Standard size: NEC 240.6(A)

Poles: 1-pole

Assumptions Used

NEC 210.20(A) continuous-load 125% factor, NEC 240.6(A) standard ampere ratings. GFCI/AFCI flags are a general dwelling-unit planning reference per NEC 210.8/210.12 — always confirm against local code amendments. This is a reference estimate — confirm with a licensed electrician before final installation.

Need to find the right wire size for this breaker from scratch? Wire Size Calculator →

Checking a long run's voltage drop instead? Voltage Drop Calculator →

Breaker Panel VisualizationPanel20A1-pole20.0 ADiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Circuit Breaker Size Calculator.

Kitchen circuit breaker sizing

Kitchen countertop receptacle circuits are commonly 20A (sometimes required as dedicated small-appliance circuits) and typically require both GFCI and AFCI protection — this page is pre-set to that scenario.

Edit the load above to match your actual kitchen circuit; the GFCI/AFCI flags stay tied to the Kitchen location.

  • Kitchen countertop receptacles require GFCI protection per NEC 210.8(A)(6).
  • Kitchen circuits also require AFCI protection per NEC 210.12 in most dwelling-unit applications.
  • A combination dual-function breaker is commonly used to provide both protections in one device.

Circuit Breaker Formula: How Is Size Calculated?

The core calculation is the same whether there's one load or several sharing a circuit — the difference is how the design current is built up before rounding to a standard size.

Step 1 — Design Current per Load

Design Current = Load Current × 1.25 (if continuous — 3+ hours)

Design Current = Load Current (if not continuous)

Per NEC 210.20(A), a continuous load needs a 25% safety margin; a non-continuous load uses its actual current directly. This is applied per load before combining multiple loads onto one circuit.

Step 2 — Combined Design Current (Multiple Loads)

Total Design Current = Sum of every load's own Design Current

When several loads share one circuit, sum each load's own design current (not the raw currents first, then apply 125% once) — mathematically identical to NEC's own phrasing of noncontinuous-sum plus 125% of continuous-sum, since multiplication distributes over the sum.

Step 3 — Standard Breaker Size

Recommended Breaker = smallest NEC 240.6(A) standard rating ≥ Total Design Current

Standard ampere ratings (15, 20, 25, 30, 35, 40, 45, 50, 60A, and larger) come from NEC 240.6(A) — a breaker is always sized up to the next standard rating, never to a custom in-between value.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Load(s)16.0 A (continuous)Sets the total design current
System120 V, single-phaseSets number of poles
LocationKitchen (countertop receptacles)Sets GFCI/AFCI requirement flags

Step 1 — Design Current

CalculationResult
Total base current16.0 A
Total design current20.0 A

Therefore, for 20.0A of design current at 120V, you need a 20A, 1-pole breaker, with GFCI and AFCI protection required for kitchen (countertop receptacles).

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

20A is common for kitchen countertop small-appliance circuits, often required as dedicated circuits separate from general lighting — confirm the specific requirement for your kitchen's countertop receptacle count and layout.
Typically yes under current NEC editions — kitchen countertop receptacles need GFCI protection, and kitchen circuits generally need AFCI protection, commonly combined in one dual-function breaker.