TryBuildCalc

3-Phase Breaker Size Calculator (Three-Phase Circuit Sizing)

Calculate 3-phase breaker size.

Inputs

Multiple Loads on One Circuit?
Load Entered As
A
Continuous Load (3+ hours)?
V

ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).

ℹ️Flags GFCI (NEC 210.8) and AFCI (NEC 210.12) protection requirements for dwelling units — always confirm against local code amendments.

Wire Cross-Check

Cross-Check Against a Specific Wire Size?

Cost

Enable Cost Estimation?

Recommended Breaker: 50A (3-pole)

From 50.0A design current at 480V, three-phase

Circuit Summary

Design current basis: NEC 210.20(A) — 100% non-continuous + 125% continuous

Standard size: NEC 240.6(A)

Poles: 3-pole

Assumptions Used

NEC 210.20(A) continuous-load 125% factor, NEC 240.6(A) standard ampere ratings. GFCI/AFCI flags are a general dwelling-unit planning reference per NEC 210.8/210.12 — always confirm against local code amendments. This is a reference estimate — confirm with a licensed electrician before final installation.

Need to find the right wire size for this breaker from scratch? Wire Size Calculator →

Checking a long run's voltage drop instead? Voltage Drop Calculator →

Breaker Panel VisualizationPanel50A3-pole50.0 ADiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Circuit Breaker Size Calculator.

Three-phase breaker sizing

Three-phase circuits are typically protected by a 3-pole breaker — this page is pre-set to a common commercial three-phase scenario at 480V.

Edit the load, voltage, or continuous status above to check your actual three-phase circuit.

  • Three-phase circuits use a 3-pole breaker, switching all three phase conductors together.
  • The same 125% continuous-load factor and NEC 240.6(A) standard sizes apply regardless of phase.
  • Switch Phase back to Single-phase for a standard residential branch circuit instead.

Circuit Breaker Formula: How Is Size Calculated?

The core calculation is the same whether there's one load or several sharing a circuit — the difference is how the design current is built up before rounding to a standard size.

Step 1 — Design Current per Load

Design Current = Load Current × 1.25 (if continuous — 3+ hours)

Design Current = Load Current (if not continuous)

Per NEC 210.20(A), a continuous load needs a 25% safety margin; a non-continuous load uses its actual current directly. This is applied per load before combining multiple loads onto one circuit.

Step 2 — Combined Design Current (Multiple Loads)

Total Design Current = Sum of every load's own Design Current

When several loads share one circuit, sum each load's own design current (not the raw currents first, then apply 125% once) — mathematically identical to NEC's own phrasing of noncontinuous-sum plus 125% of continuous-sum, since multiplication distributes over the sum.

Step 3 — Standard Breaker Size

Recommended Breaker = smallest NEC 240.6(A) standard rating ≥ Total Design Current

Standard ampere ratings (15, 20, 25, 30, 35, 40, 45, 50, 60A, and larger) come from NEC 240.6(A) — a breaker is always sized up to the next standard rating, never to a custom in-between value.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Load(s)40.0 A (continuous)Sets the total design current
System480 V, three-phaseSets number of poles
LocationNot a Dwelling-Unit Circuit (commercial/industrial)Sets GFCI/AFCI requirement flags

Step 1 — Design Current

CalculationResult
Total base current40.0 A
Total design current50.0 A

Therefore, for 50.0A of design current at 480V, you need a 50A, 3-pole breaker.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

A 3-pole breaker switches all three phase conductors together as one unit, ensuring the circuit is fully de-energized (or protected) on all three phases simultaneously — standard practice for three-phase circuits.
Yes — NEC 210.20(A)'s continuous-load factor applies regardless of phase configuration; only the current calculation itself (when sizing from watts) differs by phase.