TryBuildCalc

Circuit Breaker Size Calculator (NEC 210.20 / 240.6 — Single or Multiple Loads)

Calculate breaker size instantly.

Inputs

Multiple Loads on One Circuit?
Load Entered As
A
Continuous Load (3+ hours)?
V

ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).

ℹ️Determines pole count — voltage alone doesn't tell you this. 120V and 277V circuits are typically line-to-neutral (1-pole); 240V split-phase and 208V are typically line-to-line (2-pole).

ℹ️Flags GFCI (NEC 210.8) and AFCI (NEC 210.12) protection requirements for dwelling units — always confirm against local code amendments.

Wire Cross-Check

Cross-Check Against a Specific Wire Size?

Cost

Enable Cost Estimation?

Recommended Breaker: 20A (1-pole)

From 16.0A design current at 120V, single-phase

Protection Required — General / Other (living area, hallway, closet)

• AFCI protection required (NEC 210.12(A))

Circuit Summary

Design current basis: NEC 210.20(A) — 100% non-continuous + 125% continuous

Standard size: NEC 240.6(A)

Poles: 1-pole

Assumptions Used

NEC 210.20(A) continuous-load 125% factor, NEC 240.6(A) standard ampere ratings. GFCI/AFCI flags are a general dwelling-unit planning reference per NEC 210.8/210.12 — always confirm against local code amendments. This is a reference estimate — confirm with a licensed electrician before final installation.

Need to find the right wire size for this breaker from scratch? Wire Size Calculator →

Checking a long run's voltage drop instead? Voltage Drop Calculator →

Breaker Panel VisualizationPanel20A1-pole16.0 ADiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Circuit Breaker Size Calculator.

General circuit breaker size estimate

This page gives the full combined breaker-sizing result — design current, recommended standard breaker, poles, and GFCI/AFCI flags — from one set of load and location inputs.

It's the same calculator behind every other breaker-sizing variant on this site, just without a specific scenario pre-selected — useful for a general check before finalizing the exact circuit.

  • Applies the NEC 210.20(A) 125% continuous-load factor automatically.
  • Combine multiple loads sharing one circuit into a single breaker recommendation.
  • Flags GFCI/AFCI protection requirements by circuit location.

Circuit Breaker Formula: How Is Size Calculated?

The core calculation is the same whether there's one load or several sharing a circuit — the difference is how the design current is built up before rounding to a standard size.

Step 1 — Design Current per Load

Design Current = Load Current × 1.25 (if continuous — 3+ hours)

Design Current = Load Current (if not continuous)

Per NEC 210.20(A), a continuous load needs a 25% safety margin; a non-continuous load uses its actual current directly. This is applied per load before combining multiple loads onto one circuit.

Step 2 — Combined Design Current (Multiple Loads)

Total Design Current = Sum of every load's own Design Current

When several loads share one circuit, sum each load's own design current (not the raw currents first, then apply 125% once) — mathematically identical to NEC's own phrasing of noncontinuous-sum plus 125% of continuous-sum, since multiplication distributes over the sum.

Step 3 — Standard Breaker Size

Recommended Breaker = smallest NEC 240.6(A) standard rating ≥ Total Design Current

Standard ampere ratings (15, 20, 25, 30, 35, 40, 45, 50, 60A, and larger) come from NEC 240.6(A) — a breaker is always sized up to the next standard rating, never to a custom in-between value.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Load(s)16.0 ASets the total design current
System120 V, single-phaseSets number of poles
LocationGeneral / Other (living area, hallway, closet)Sets GFCI/AFCI requirement flags

Step 1 — Design Current

CalculationResult
Total base current16.0 A
Total design current16.0 A

Therefore, for 16.0A of design current at 120V, you need a 20A, 1-pole breaker, with AFCI protection required for general / other (living area, hallway, closet).

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

Yes — mark a load as continuous and the calculator applies NEC 210.20(A)'s 125% factor before rounding to a standard breaker size.
Yes — turn on Multiple Loads mode to add several loads sharing one circuit, and the calculator sums their design currents into one combined breaker recommendation.