Complete these critical checks before approving the work or proceeding to the next construction stage.

βœ“15 Inspection Points
βœ“5 Verification Categories
βœ“Load & Circuit Inputs+
  • Load current confirmed from equipment nameplate, not estimated
  • Continuous vs. non-continuous load correctly classified
  • System voltage and phase confirmed against the actual panel/service
  • Run length measured as actual one-way routed distance, not straight-line or round-trip
βœ“Ampacity & Derating+
  • Insulation temperature rating and terminal/equipment rating entered separately, not assumed equal
  • 14/12/10 AWG copper conductors capped at 15A/20A/30A breaker regardless of table ampacity
  • Conductor-count derating applied when more than 3 current-carrying conductors share a raceway
  • Aluminum conductor terminations confirmed AL-rated (not CU-only)
βœ“Voltage Drop+
  • Voltage drop checked independently of the ampacity result, not assumed to be fine
βœ“Installation & Code Compliance+
  • Breaker/OCPD size does not exceed the selected conductor's allowable ampacity or small-conductor cap
  • Local code edition and any local amendments confirmed before finalizing
  • Permit and inspection requirements confirmed for the scope of work
  • Work beyond a simple, single branch circuit reviewed or performed by a licensed electrician
βœ“Conduit Sizing+
  • Conduit fill checked as a separate NEC Chapter 9 requirement, not assumed covered by the ampacity result
  • Total conductor count for fill purposes includes every physical conductor, including the equipment grounding conductor
Full QC Checklist+

Verify load classification, ampacity and derating, voltage drop, and code compliance.

βœ“23 Inspection Points
βœ“5 Verification Categories
βœ“Load & Circuit Inputs+
  • Load current confirmed from equipment nameplate, not estimated
  • Continuous vs. non-continuous load correctly classified
  • System voltage and phase confirmed against the actual panel/service
  • Run length measured as actual one-way routed distance, not straight-line or round-trip
  • Power factor entered correctly when sizing from a wattage nameplate rating on a motor or reactive load
βœ“Ampacity & Derating+
  • Insulation temperature rating and terminal/equipment rating entered separately, not assumed equal
  • 14/12/10 AWG copper conductors capped at 15A/20A/30A breaker regardless of table ampacity
  • Conductor-count derating applied when more than 3 current-carrying conductors share a raceway
  • Ambient temperature correction applied for hot locations (attics, rooftops, outdoor conduit in sun)
  • Aluminum conductor terminations confirmed AL-rated (not CU-only)
  • Cable run through or in contact with thermal insulation checked against the cable-type-specific derating rule
βœ“Voltage Drop+
  • Voltage drop checked independently of the ampacity result, not assumed to be fine
  • Maximum voltage drop percentage matched to the load's actual sensitivity
  • Detached structures, well pumps, and other long runs specifically flagged for voltage-drop review
  • Single-phase vs. three-phase voltage-drop multiplier confirmed correct for the actual circuit
βœ“Installation & Code Compliance+
  • Breaker/OCPD size does not exceed the selected conductor's allowable ampacity or small-conductor cap
  • Conductor color coding (hot, neutral, ground) follows local code convention, consistently across the circuit
  • Local code edition and any local amendments confirmed before finalizing
  • Permit and inspection requirements confirmed for the scope of work
  • Work beyond a simple, single branch circuit reviewed or performed by a licensed electrician
βœ“Conduit Sizing+
  • Conduit fill checked as a separate NEC Chapter 9 requirement, not assumed covered by the ampacity result
  • Total conductor count for fill purposes includes every physical conductor, including the equipment grounding conductor
  • Conduit type selected matches what will actually be installed (EMT, PVC Schedule 40, or RMC)
Inspection Notes+
Use the latest approved drawings, specifications, and site measurements.
Complete all critical checks before proceeding to the next work stage.
Record deviations and confirm rectification where required.