TryBuildCalc

Generator Wire Size Calculator (Generator-to-Panel Feeder Sizing)

Size generator feeder wire.

Inputs

Load Entered As
A
V

ℹ️Common values: 120V, 208V, 240V, 277V, 480V (US); 230V, 400V (many other countries).

ℹ️Distance from the panel/breaker to the load, one way — not round trip.

ℹ️The wire's own insulation rating (check the product's markings, e.g. THHN, THWN-2).

ℹ️Per NEC 110.14(C) — the breaker/panel/device's own temperature rating. Most equipment rated 100A or less is only terminal-rated for 60°C or 75°C, even with 90°C wire installed. The calculator automatically uses the lower of this and the insulation rating above.

Continuous Load (3+ hours)?

Advanced (NEC Derating)

Adjust for Conductor Count / Ambient Temperature?

Conduit Sizing

Also Size the Conduit?

Cost

Enable Cost Estimation?

Recommended Wire Size: 8 AWG (Copper)

Sized by ampacity, not voltage drop — recommended breaker/OCPD: 40A

Ampacity Check

Design current: 40.0 A

Minimum size by ampacity: 8 AWG

Derating factor applied: 1.00×

Final wire's derated ampacity: 50.0 A

Voltage Drop Check

Actual load current: 40.0 A

Minimum size by voltage drop: 8 AWG

Allowed drop: 3.0%

Final wire's actual drop: 1.95% (4.69 V)

Circuit Summary

System240 V, single-phase
One-way run length75.0 ft (22.9 m)
Insulation / terminal rating75°C (167°F) — most common (THWN-2, terminals) / 75°C (167°F) — most common (THWN-2, terminals)
Governing rating (NEC 110.14(C))75°C (167°F) — most common (THWN-2, terminals)

Assumptions Used

NEC Table 310.16 ampacity, NEC 110.14(C) governing rating, NEC 240.4(D) small-conductor cap, NEC 310.15(C)(1)/(B)(1)(1) derating, NEC Chapter 9 conduit fill (THHN/THWN-2, uniform AWG). Voltage drop uses K = 12.9 (copper) / 21.2 (aluminum) ohm-cmil/ft. This is a reference estimate — confirm against the code edition adopted in your jurisdiction and a licensed electrician before final installation.

Wire Run VisualizationPanelLoad8 AWG40.0 ALength: 75 ftDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Wire Size Calculator.

Generator feeder wire sizing

A standby or large portable generator is often installed some distance from the house's transfer switch or panel — this page is pre-set to a 75ft run at a common 40A generator output.

Edit the load (matching your specific generator's rated output), voltage, and length above to size the actual feeder for your installation.

  • Use the generator's actual rated output current or wattage, not an assumed figure.
  • Outdoor generator-to-panel runs are a common case where voltage drop governs over ampacity.
  • Confirm local code requirements for generator interconnection — this typically needs a permitted transfer switch, not just a feeder wire.

Wire Size Formula: How Is AWG Gauge Calculated?

Two independent checks are run, and the wire recommended is whichever check requires the larger conductor.

Step 1 — Design Current

Design Current = Load Current × 1.25 (if continuous load, per NEC 210.19/210.20)

Design Current = Load Current (if not continuous)

A continuous load (running 3+ hours) needs a 25% safety margin applied to the wire and breaker sizing, per NEC's continuous-load rule. Voltage drop, further below, uses the actual (non-inflated) current instead.

Step 2 — Ampacity Check

Governing Rating = the LOWER of Insulation Rating and Terminal/Equipment Rating (NEC 110.14(C))

Derated Ampacity = Table Ampacity (at Governing Rating) × Conductor-Count Factor × Ambient-Temp Factor

Pick the smallest AWG where Derated Ampacity ≥ Design Current

Table ampacity comes from NEC Table 310.16, by material (copper/aluminum) and the governing 60/75/90°C column — not just the wire's own insulation rating, since most equipment rated 100A or less is only terminal-rated for 60°C or 75°C even when 90°C wire is installed. 14/12/10 AWG are additionally capped at 15A/20A/30A (copper) regardless of table ampacity, per NEC 240.4(D).

Step 3 — Voltage Drop Check

Voltage Drop (V) = (2 × K × I × D) / CM [single-phase]

Voltage Drop (V) = (1.732 × K × I × D) / CM [three-phase]

Pick the smallest AWG where (Voltage Drop ÷ System Voltage) × 100 ≤ Max Allowed %

K is a resistivity constant (12.9 for copper, 21.2 for aluminum, ohm-circular-mil/ft), I is the actual load current, D is the one-way run length in feet, and CM is the conductor's circular-mil area.

Step 4 — Final Recommendation

Recommended AWG = the larger of the ampacity-check size and the voltage-drop-check size

Both requirements must be satisfied at once, so the calculator always recommends whichever check needs the bigger conductor — never just the smaller of the two.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Load current / voltage40.0 A, 240 V, single-phaseSets design current and the voltage-drop base
Material / rating / lengthCopper, governed by 75°C (167°F) — most common (THWN-2, terminals), 75.0 ftSets ampacity table column (lower of insulation/terminal rating) and voltage-drop distance
Derating / max drop1.00× derate, 3.0% max dropSets the derated ampacity and voltage-drop threshold

Step 1 — Ampacity Check

CalculationResult
Design current40.0 A
Minimum size by ampacity8 AWG

Step 2 — Voltage Drop Check

CalculationResult
Minimum size by voltage drop8 AWG
Final recommended size8 AWG (governed by ampacity)

Therefore, for a 40.0A load over 75.0 ft at 240V, you need approximately 8 AWG copper wire on a 40A breaker.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

Use the generator's actual rated continuous output current or wattage from its nameplate/spec sheet, not the connected appliance loads — the feeder needs to be sized to what the generator itself can supply.
Generators are frequently installed outdoors, some distance from the transfer switch or panel, making the run long enough for voltage drop to govern — check both the ampacity and voltage-drop results, not just ampacity.