200 Amp Service Calculator (Load Check for a 200A Dwelling Service)

Check your load against a 200A service.

Inputs

sq ft

ℹ️Outside-dimension floor area per NEC 220.82 — excludes open porches, garages, and unfinished/unused spaces not adaptable for future use.

ℹ️NEC 220.52(A) requires a minimum of 2 (1,500 VA each) — this calculator enforces that floor automatically.

ℹ️NEC 220.52(B) requires a minimum of 1 (1,500 VA) — this calculator enforces that floor automatically.

Fixed-in-Place Appliances

Include every permanently connected appliance — range, dryer, water heater, dishwasher, disposal, and similar — at full nameplate VA/watts. Don't include portable, cord-and-plug appliances.

Appliance 1

VA

Appliance 2

VA

Appliance 3

VA

Appliance 4

VA

Heating / Cooling

ℹ️NEC 220.82(C) uses only the larger of heating or cooling load, never both added together.

VA
VA

ℹ️Counted at 65% demand factor, per NEC 220.82(C).

Cost

Enable Cost Estimation?

Recommended Service/Panel Size: 150A

From 30,340 VA total demand load at 240V (126.4A)

Load Breakdown (NEC 220.82 Optional Calculation)

General lighting + receptacle load (2,800 sq ft × 3 VA)8,400 VA
Small-appliance circuits (2 × 1500 VA)3,000 VA
Laundry circuit(s) (1 × 1500 VA)1,500 VA
Range8,000 VA
Dryer5,500 VA
Water Heater4,500 VA
Dishwasher1,200 VA
Subtotal32,100 VA
After demand factor (100% of first 10,000 VA + 40% of remainder)18,840 VA
Heating/cooling load (Heat Pump with Supplemental Electric Heat)11,500 VA
Total demand load30,340 VA

Service Sizing

Total demand current: 126.4A

Recommended standard service: 150A

Headroom above calculated demand: 23.6A (15.7%)

Assumptions Used

NEC 220.82 Optional Calculation for dwelling units — a single 120/240V or 208Y/120V service ≥100A. Heating and cooling loads are never added together, only the larger is used. This is a reference estimate — confirm with a licensed electrician before final installation.

Sizing an individual circuit's breaker next? Circuit Breaker Size Calculator →

Need the feeder or service wire size for this load? Wire Size Calculator →

Service Panel SizingUtility Service150ATotal Demand30,340 VAHeadroom23.6 ADiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Electrical Load / Panel Size Calculator.

200A service load check

200A is the most common service size for a modern single-family home with electric heat, central A/C, or a heat pump — this page is pre-set to a larger home with a heat pump and supplemental electric heat.

Edit the inputs above to check whether your actual home fits 200A or needs a different standard size.

  • 200A is the most common size for a modern 3-4 bedroom single-family home.
  • A heat pump with supplemental electric heat is one of the loads most likely to push a home from 100A/150A up to 200A.
  • Increase floor area, appliances, or HVAC load above to see when 200A is no longer sufficient.

Panel Size Formula: How Is Service Size Calculated?

NEC 220.82 combines a general load subtotal (subject to one demand factor) with a separate heating/cooling load, then rounds the total current up to a standard service size.

Step 1 — General Load Subtotal

General Load = (Floor Area × 3 VA) + (Small-Appliance Circuits × 1,500 VA)

+ (Laundry Circuits × 1,500 VA) + Sum of Fixed Appliance Nameplate VA

Per NEC 220.82(B), general lighting/receptacle load, small-appliance and laundry circuits, and every fixed-in-place appliance (including range and dryer, at full nameplate VA) are all summed into one subtotal.

Step 2 — Apply the Demand Factor

General Demand = 100% of first 10,000 VA + 40% of the remainder above 10,000 VA

This single demand factor reflects that not every load in the general subtotal runs at full power simultaneously — it's applied to the general subtotal only, before the heating/cooling load is added.

Step 3 — Add the Larger of Heating or Cooling

Total Demand = General Demand + MAX(Heating Load, Cooling Load)

Per NEC 220.82(C), heating and cooling are never added together — only the larger of the two is included, since a dwelling's heating and cooling equipment isn't assumed to run simultaneously.

Step 4 — Convert to Current and Round to a Standard Size

Total Demand Current = Total Demand (VA) ÷ Voltage

Recommended Service = smallest standard size ≥ Total Demand Current

Standard dwelling service sizes (100, 125, 150, 200, 225, 300, 400A) come from what's actually manufactured and installed — the calculated current is always rounded up, never down.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Floor Area2,800 sq ftSets general lighting/receptacle load
Fixed Appliances4 appliances, 19,200 VAAdded to general subtotal before demand factor
HVACHeat Pump with Supplemental Electric HeatSets the heating/cooling load added after demand factor

Steps 1-2 — General Load and Demand Factor

CalculationResult
General load subtotal32,100 VA
After 10,000 VA / 40% demand factor18,840 VA
Heating/cooling load (Heat Pump with Supplemental Electric Heat)11,500 VA
Total demand load30,340 VA

Therefore, for 30,340 VA of total demand load at 240V (126.4A), you need a 150A service/panel.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

For many modern single-family homes with electric heat or a heat pump, yes — but larger homes, all-electric homes, or homes adding significant future load (like an EV charger) can exceed 200A. Calculate your actual load rather than assuming.
Electric heat (space heating or a heat pump), a larger floor area, and a full set of major fixed appliances are the most common drivers — an all-gas home with modest floor area can often stay at 100A or 150A.