100 Amp Panel Calculator (Load Check for a 100A Dwelling Service)

Check your load against a 100A service.

Inputs

sq ft

ℹ️Outside-dimension floor area per NEC 220.82 — excludes open porches, garages, and unfinished/unused spaces not adaptable for future use.

ℹ️NEC 220.52(A) requires a minimum of 2 (1,500 VA each) — this calculator enforces that floor automatically.

ℹ️NEC 220.52(B) requires a minimum of 1 (1,500 VA) — this calculator enforces that floor automatically.

Fixed-in-Place Appliances

Include every permanently connected appliance — range, dryer, water heater, dishwasher, disposal, and similar — at full nameplate VA/watts. Don't include portable, cord-and-plug appliances.

Appliance 1

VA

Appliance 2

VA

Heating / Cooling

ℹ️NEC 220.82(C) uses only the larger of heating or cooling load, never both added together.

VA

Cost

Enable Cost Estimation?

Recommended Service/Panel Size: 100A

From 14,020 VA total demand load at 240V (58.4A)

Load Breakdown (NEC 220.82 Optional Calculation)

General lighting + receptacle load (1,200 sq ft × 3 VA)3,600 VA
Small-appliance circuits (2 × 1500 VA)3,000 VA
Laundry circuit(s) (1 × 1500 VA)1,500 VA
Water Heater4,500 VA
Dishwasher1,200 VA
Subtotal13,800 VA
After demand factor (100% of first 10,000 VA + 40% of remainder)11,520 VA
Heating/cooling load (Air Conditioning Only)2,500 VA
Total demand load14,020 VA

Service Sizing

Total demand current: 58.4A

Recommended standard service: 100A

Headroom above calculated demand: 41.6A (41.6%)

Assumptions Used

NEC 220.82 Optional Calculation for dwelling units — a single 120/240V or 208Y/120V service ≥100A. Heating and cooling loads are never added together, only the larger is used. This is a reference estimate — confirm with a licensed electrician before final installation.

Sizing an individual circuit's breaker next? Circuit Breaker Size Calculator →

Need the feeder or service wire size for this load? Wire Size Calculator →

Service Panel SizingUtility Service100ATotal Demand14,020 VAHeadroom41.6 ADiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Electrical Load / Panel Size Calculator.

100A panel load check

100A is NEC 220.82's minimum standard service size — this page is pre-set to a smaller home without electric space heating, a common scenario where 100A remains adequate.

Edit the inputs above to see how much headroom your actual smaller home has, or whether it pushes past 100A.

  • 100A is the smallest service size NEC 220.82's Optional Calculation applies to.
  • Homes without electric space heating (gas furnace, gas water heater) commonly stay comfortably within 100A.
  • Adding electric space heat or a heat pump is the most common reason a 100A home needs to move up to 150A or 200A.

Panel Size Formula: How Is Service Size Calculated?

NEC 220.82 combines a general load subtotal (subject to one demand factor) with a separate heating/cooling load, then rounds the total current up to a standard service size.

Step 1 — General Load Subtotal

General Load = (Floor Area × 3 VA) + (Small-Appliance Circuits × 1,500 VA)

+ (Laundry Circuits × 1,500 VA) + Sum of Fixed Appliance Nameplate VA

Per NEC 220.82(B), general lighting/receptacle load, small-appliance and laundry circuits, and every fixed-in-place appliance (including range and dryer, at full nameplate VA) are all summed into one subtotal.

Step 2 — Apply the Demand Factor

General Demand = 100% of first 10,000 VA + 40% of the remainder above 10,000 VA

This single demand factor reflects that not every load in the general subtotal runs at full power simultaneously — it's applied to the general subtotal only, before the heating/cooling load is added.

Step 3 — Add the Larger of Heating or Cooling

Total Demand = General Demand + MAX(Heating Load, Cooling Load)

Per NEC 220.82(C), heating and cooling are never added together — only the larger of the two is included, since a dwelling's heating and cooling equipment isn't assumed to run simultaneously.

Step 4 — Convert to Current and Round to a Standard Size

Total Demand Current = Total Demand (VA) ÷ Voltage

Recommended Service = smallest standard size ≥ Total Demand Current

Standard dwelling service sizes (100, 125, 150, 200, 225, 300, 400A) come from what's actually manufactured and installed — the calculated current is always rounded up, never down.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Floor Area1,200 sq ftSets general lighting/receptacle load
Fixed Appliances2 appliances, 5,700 VAAdded to general subtotal before demand factor
HVACAir Conditioning OnlySets the heating/cooling load added after demand factor

Steps 1-2 — General Load and Demand Factor

CalculationResult
General load subtotal13,800 VA
After 10,000 VA / 40% demand factor11,520 VA
Heating/cooling load (Air Conditioning Only)2,500 VA
Total demand load14,020 VA

Therefore, for 14,020 VA of total demand load at 240V (58.4A), you need a 100A service/panel.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

It's the code minimum for NEC 220.82 sizing and can be adequate for a smaller home without electric heat — but many electricians recommend 150A or 200A for headroom against future additions like an EV charger.
NEC 220.82's Optional Calculation is explicitly defined for a dwelling service rated 100A or larger — this calculator's standard size list starts there.