TryBuildCalc

Heat Pump MCA & MOCP Calculator (NEC Article 440)

Size the circuit for a heat pump.

Inputs

Input Method
A

ℹ️Minimum Circuit Ampacity, printed directly on the equipment's nameplate — this sets the minimum required wire ampacity.

A

ℹ️Maximum Overcurrent Protection (sometimes labeled MOP or MFS for max fuse size), printed directly on the nameplate — this sets the maximum allowed breaker/fuse size.

ℹ️Copper and aluminum have different ampacity tables — aluminum needs a larger wire size for the same MCA.

ℹ️The wire's own temperature rating (e.g. THHN is 90°C).

ℹ️Per NEC 110.14(C), the equipment/breaker terminal rating governs if it's lower than the wire's own insulation rating — most residential equipment is rated 60°C or 75°C even when 90°C wire is used.

Derating

Apply Ambient Temperature / Conductor Count Derating?

Cost

Enable Cost Estimation?

Wire Size (Copper)

10 AWG

Breaker / Fuse Size

40 A

MCA — Minimum Circuit Ampacity

MCA used: 24 A

Wire ampacity (base): 35 A

Entered directly from nameplate

MOCP — Max Overcurrent Protection

MOCP used: 40 A

Entered directly from nameplate

Assumptions Used

NEC Article 440 (440.32 MCA, 440.22 MOCP), NEC Table 310.16 conductor ampacity, NEC 240.6(A) standard overcurrent device sizes. Manufacturer nameplate MCA/MOCP values, where marked, take precedence over any from-scratch calculation — this reflects UL listing testing specific to that equipment. The 175%-to-225% MOCP rounding step has genuinely documented interpretation differences across published sources (see the note above when calculating from component ratings). This is a reference estimate — confirm against the code edition adopted in your jurisdiction and a licensed HVAC/electrical contractor before final installation.

Want the full walkthrough on MCA vs. MOCP vs. RLA/FLA, and the 175%/225% rounding rule? MCA & MOCP Sizing Guide →

MCA / MOCP Circuit SizingPanel40 A Breaker10 AWG (copper)AC / CompressorWire sized to MCA — breaker sized to MOCPDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete MCA & MOCP Calculator.

Heat pump condenser circuit sizing

A heat pump's outdoor condenser unit is sized the same way as a central AC condenser — this page focuses on that outdoor unit's circuit, separate from any indoor electric backup heat strip circuit.

This page is pre-set to a common residential heat pump's MCA/MOCP range — edit the inputs above to match your actual unit's nameplate.

  • The outdoor heat pump condenser and an indoor air handler's electric backup heat strips are typically on two SEPARATE circuits with their own nameplate MCA/MOCP each — don't combine them into one calculation unless the equipment's nameplate explicitly does so.
  • Electric heat strips add a real load consideration beyond this calculator's simplified from-scratch model — always use the nameplate value for equipment with integrated backup heat.
  • Cold-climate heat pumps can have a different MCA/MOCP than a standard-climate model of similar cooling capacity — always check the specific unit's nameplate.

MCA & MOCP Formula: How Are They Determined?

Two independent NEC 440 calculations from the same motor/load data, followed by translating each into an actual standard wire and breaker size.

Step 1 — MCA (NEC 440.32/440.33)

MCA = (1.25 × Largest Motor RLA/FLA) + Other Motor Loads + Other Non-Motor Loads

Wire Size = smallest standard AWG/kcmil whose (derated) ampacity ≥ MCA

Only the single largest motor gets the 125% factor — every other motor and non-motor load on the circuit is added at 100%.

Step 2 — MOCP (NEC 440.22)

Base = (1.75 × Largest Motor RLA/FLA) + Other Loads, rounded UP to the next standard size

Cap = (2.25 × Largest Motor RLA/FLA) + Other Loads

MOCP = the rounded-up value, UNLESS it exceeds the cap — then round DOWN to the largest standard size within the cap

Breaker/Fuse Size = the resulting MOCP value directly

The 175%→225% range exists specifically to accommodate a motor-compressor's startup inrush current without nuisance tripping, while the 225% figure is a hard ceiling that can never be exceeded regardless of standard-size rounding. Published NEC sources genuinely disagree on whether rounding up to the next standard size is the routine default (used above) or should be reserved for a demonstrated starting-current problem, with a more conservative round-down-by-default reading otherwise — the calculator surfaces both values when calculating from component ratings; confirm the preferred interpretation with a licensed electrician or your local AHJ.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Input methodNameplate valuesDetermines whether MCA/MOCP are entered directly or calculated
Wire materialCopperSets which NEC Table 310.16 ampacity column governs the wire size

Step 1 — MCA

CalculationResult
MCA24 A
Wire size10 AWG (copper)

Step 2 — MOCP

CalculationResult
MOCP40 A (from nameplate)
Breaker/fuse size40 A

Therefore, for this equipment you need approximately 10 AWG copper wire on a 40 A breaker/fuse.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

The MCA/MOCP calculation method itself (NEC Article 440) is the same — the difference is mainly in the equipment's actual nameplate values, since a heat pump's compressor and any reversing-valve/defrost components can differ from a straight-cooling-only AC's.
Almost always yes, sized separately from the outdoor condenser's MCA/MOCP-based circuit — treat the air handler's electric heat kit as its own calculation using its own nameplate values.