TryBuildCalc

Central AC MCA & MOCP Calculator (Nameplate MCA/MOCP)

Size the circuit for a central AC unit.

Inputs

Input Method
A

ℹ️Minimum Circuit Ampacity, printed directly on the equipment's nameplate — this sets the minimum required wire ampacity.

A

ℹ️Maximum Overcurrent Protection (sometimes labeled MOP or MFS for max fuse size), printed directly on the nameplate — this sets the maximum allowed breaker/fuse size.

ℹ️Copper and aluminum have different ampacity tables — aluminum needs a larger wire size for the same MCA.

ℹ️The wire's own temperature rating (e.g. THHN is 90°C).

ℹ️Per NEC 110.14(C), the equipment/breaker terminal rating governs if it's lower than the wire's own insulation rating — most residential equipment is rated 60°C or 75°C even when 90°C wire is used.

Derating

Apply Ambient Temperature / Conductor Count Derating?

Cost

Enable Cost Estimation?

Wire Size (Copper)

10 AWG

Breaker / Fuse Size

35 A

MCA — Minimum Circuit Ampacity

MCA used: 21 A

Wire ampacity (base): 35 A

Entered directly from nameplate

MOCP — Max Overcurrent Protection

MOCP used: 35 A

Entered directly from nameplate

Assumptions Used

NEC Article 440 (440.32 MCA, 440.22 MOCP), NEC Table 310.16 conductor ampacity, NEC 240.6(A) standard overcurrent device sizes. Manufacturer nameplate MCA/MOCP values, where marked, take precedence over any from-scratch calculation — this reflects UL listing testing specific to that equipment. The 175%-to-225% MOCP rounding step has genuinely documented interpretation differences across published sources (see the note above when calculating from component ratings). This is a reference estimate — confirm against the code edition adopted in your jurisdiction and a licensed HVAC/electrical contractor before final installation.

Want the full walkthrough on MCA vs. MOCP vs. RLA/FLA, and the 175%/225% rounding rule? MCA & MOCP Sizing Guide →

MCA / MOCP Circuit SizingPanel35 A Breaker10 AWG (copper)AC / CompressorWire sized to MCA — breaker sized to MOCPDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete MCA & MOCP Calculator.

Central AC / heat pump condenser circuit sizing

A residential central air conditioner or heat pump condenser is the single most common real-world use case for MCA/MOCP sizing — the outdoor unit's nameplate has both values printed directly on it.

This page is pre-set to a common residential condenser's MCA/MOCP range — edit the inputs above to match your actual unit's nameplate.

  • Read the MCA and MOCP directly off the outdoor unit's nameplate — usually located on a data plate inside the service panel cover.
  • MOCP is sometimes labeled MOP (Maximum Overcurrent Protection) or MFS (Maximum Fuse Size) depending on the manufacturer.
  • Don't forget a separate equipment grounding conductor, sized from the breaker's rating per NEC Table 250.122.

MCA & MOCP Formula: How Are They Determined?

Two independent NEC 440 calculations from the same motor/load data, followed by translating each into an actual standard wire and breaker size.

Step 1 — MCA (NEC 440.32/440.33)

MCA = (1.25 × Largest Motor RLA/FLA) + Other Motor Loads + Other Non-Motor Loads

Wire Size = smallest standard AWG/kcmil whose (derated) ampacity ≥ MCA

Only the single largest motor gets the 125% factor — every other motor and non-motor load on the circuit is added at 100%.

Step 2 — MOCP (NEC 440.22)

Base = (1.75 × Largest Motor RLA/FLA) + Other Loads, rounded UP to the next standard size

Cap = (2.25 × Largest Motor RLA/FLA) + Other Loads

MOCP = the rounded-up value, UNLESS it exceeds the cap — then round DOWN to the largest standard size within the cap

Breaker/Fuse Size = the resulting MOCP value directly

The 175%→225% range exists specifically to accommodate a motor-compressor's startup inrush current without nuisance tripping, while the 225% figure is a hard ceiling that can never be exceeded regardless of standard-size rounding. Published NEC sources genuinely disagree on whether rounding up to the next standard size is the routine default (used above) or should be reserved for a demonstrated starting-current problem, with a more conservative round-down-by-default reading otherwise — the calculator surfaces both values when calculating from component ratings; confirm the preferred interpretation with a licensed electrician or your local AHJ.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Input methodNameplate valuesDetermines whether MCA/MOCP are entered directly or calculated
Wire materialCopperSets which NEC Table 310.16 ampacity column governs the wire size

Step 1 — MCA

CalculationResult
MCA21 A
Wire size10 AWG (copper)

Step 2 — MOCP

CalculationResult
MOCP35 A (from nameplate)
Breaker/fuse size35 A

Therefore, for this equipment you need approximately 10 AWG copper wire on a 35 A breaker/fuse.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

Usually on a data plate mounted on the side or inside the electrical access panel of the outdoor condensing unit — look for 'MCA' and 'MOCP' (or 'MOP'/'MFS') printed near the electrical specifications.
Use the largest standard breaker/fuse size that does not exceed the nameplate MOCP — it's normal for this to be slightly below the exact MOCP number if MOCP itself doesn't land on a standard size.