TryBuildCalc

Voltage-Drop Upsized Equipment Grounding Conductor Calculator (NEC 250.122(B) — Proportional Increase)

Size an EGC after a voltage-drop upsize.

Inputs

ℹ️The equipment grounding conductor's own material — not necessarily the same as the circuit's ungrounded conductors. Table 250.122 uses genuinely different size boundaries for copper and aluminum — aluminum EGCs run one to two sizes larger than the equivalent copper size.

A

ℹ️The rating or setting of the automatic overcurrent device (breaker or fuse) protecting the circuit ahead of the equipment — not the ampacity of the circuit conductors themselves. Common standard sizes: 15, 20, 30, 40, 60, 100, 150, 200, 400A, up to 6000A for large services — an adjustable-trip breaker's actual setting (e.g. 201A) works too, since Table 250.122 keys off the OCPD's "rating or setting," not just standard sizes.

Ungrounded Conductors Upsized?

Increased for Voltage Drop or Another Reason?

ℹ️The size the ungrounded conductors would need to be based on ampacity alone, before any voltage-drop or other upsizing — from your wire-size/voltage-drop calculation.

ℹ️The larger size actually being installed. NEC 250.122(B) requires the EGC to increase in circular-mil area by the same proportion as this increase.

Cost

Enable Cost Estimation?

Required Equipment Grounding Conductor: 6 AWG (Copper)

Increased per NEC 250.122(B) — Table 250.122 alone would have called for 8 AWG

NEC Table 250.122 Lookup

OCPD (breaker/fuse) rating: 100 A

Table row: Over 60 through 100 A

Table-derived EGC size: 8 AWG

250.122(B) Upsize Check

Minimum required ungrounded size: 8 AWG

Actual installed ungrounded size: 6 AWG

Proportional increase applied: ×1.589 circular-mil area

Assumptions Used

NEC Table 250.122 (minimum size equipment grounding conductors), NEC 250.122(B) proportional increase where ungrounded conductors are upsized. Assumes a single, homogeneous conductor material for both the ungrounded conductors and the EGC, and a single (non-parallel) raceway or cable run. This is a reference estimate — confirm against the code edition adopted in your jurisdiction and a licensed electrician before final installation.

Want the full walkthrough on Table 250.122, the 250.122(B) upsize rule, and how this differs from grounding electrode conductor sizing? Equipment Grounding Conductor Sizing Guide →

Equipment Grounding ConductorPanel100 AUngrounded conductor (OCPD-protected)6 AWGEquipmentFault current returns via the EGC — not through earthDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Equipment Grounding Conductor Size Calculator.

EGC sizing after a voltage-drop upsize

It's common for a long circuit run to need larger-than-minimum ungrounded conductors to control voltage drop — but that upsize has a knock-on effect on the equipment grounding conductor that's easy to miss.

This page is pre-set to a 100A circuit with a copper EGC, where the ungrounded conductors were upsized from the 8 AWG ampacity minimum to 6 AWG for voltage drop, showing the resulting 250.122(B) proportional EGC increase — edit the inputs above to match your actual circuit.

  • NEC 250.122(B) requires the EGC to increase in circular-mil area by the same proportion as the ungrounded conductor's increase.
  • The result is always rounded up to the next standard AWG or kcmil size, never left at a non-standard value.
  • The EGC is never required to be larger than the ungrounded conductor itself, even if the proportional math would suggest otherwise.

Equipment Grounding Conductor Formula: How Is the Size Determined?

Two steps: a direct NEC Table 250.122 lookup from the OCPD rating, then a 250.122(B) proportional-increase check.

Step 1 — Table 250.122 Lookup

Find the Table 250.122 row whose OCPD-rating range contains the circuit's breaker/fuse rating

Table EGC Size = that row's EGC size, for the selected material (Cu or Al)

Table 250.122 has 19 rows, each covering a range of overcurrent device ratings, with separate copper and aluminum/copper-clad aluminum columns — sized from the OCPD rating, not the ampacity of the circuit conductors themselves.

Step 2 — 250.122(B) Proportional Increase

If ungrounded conductors were increased for voltage drop (or another reason besides temperature/conductor-count derating):

Ratio = Actual Installed Ungrounded Conductor CM ÷ Minimum Required Ungrounded Conductor CM

Final EGC = next standard size ≥ (Table EGC Size CM × Ratio), never larger than the ungrounded conductor itself

A 2020+ NEC exception also permits a qualified person to determine an alternative EGC size using engineering judgment instead of the strict circular-mil proportion — that professional-judgment path isn't modeled here, since it depends on site-specific analysis this calculator can't perform.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
OCPD rating100 ASets the Table 250.122 row
EGC materialCopperSets the Table 250.122 column
Ungrounded conductors upsized?YesDetermines whether the 250.122(B) proportional increase applies

Step 1 — Table 250.122 Lookup

CalculationResult
Table rowOver 60 through 100 A
Table-derived EGC size8 AWG

Step 2 — 250.122(B) Upsize Check

CalculationResult
Upsize checkProportional increase applied (×1.589 circular-mil area)
Final recommended size6 AWG (copper)

Therefore, for a 100 A circuit, you need approximately 6 AWG copper for the equipment grounding conductor.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

NEC 250.122(B) requires it — the code's reasoning is that the EGC's impedance relative to the ungrounded conductors needs to stay roughly proportional so fault-clearing performance isn't degraded by a disproportionately small EGC on a long, upsized run.
Not always — if the calculated proportional increase still rounds to the same standard EGC size the table would have given anyway, no practical change results. Enable the upsize toggle above and enter your actual sizes to check.