TryBuildCalc

Electrical Resources

Equipment Grounding Conductor Sizing Guide

An equipment grounding conductor provides the low-impedance fault-current return path from equipment enclosures back to the source — and it's sized from a genuinely different input than most other conductors on a circuit: the overcurrent device rating, not the wire's own ampacity. Getting it right means a direct Table 250.122 lookup, then checking whether the ungrounded conductors were upsized in a way that requires the EGC to scale up too.

Last updated: September 1, 2026

The equipment grounding conductor is easy to mis-size because it breaks the pattern set by every other conductor on the circuit — it isn't sized from ampacity, insulation rating, or the load it serves. It's sized from the overcurrent device protecting the circuit, with one specific follow-up check whenever the ungrounded conductors were upsized for another reason.

This guide covers how NEC Table 250.122 works, the 250.122(B) proportional-increase rule, copper vs. aluminum, and a full worked example.

How Table 250.122 Works

Table 250.122 sizes the EGC directly from the rating or setting of the automatic overcurrent device (breaker or fuse) protecting the circuit ahead of the equipment — with separate copper and aluminum/copper-clad aluminum columns, covering OCPD ratings from 15A branch circuits up to 6000A services.

OCPD RatingEGC — CopperEGC — Aluminum
15 A or less14 AWG12 AWG
Over 15 through 20 A12 AWG10 AWG
Over 20 through 60 A10 AWG8 AWG
Over 60 through 100 A8 AWG6 AWG
Over 100 through 200 A6 AWG4 AWG
Over 200 through 300 A4 AWG2 AWG
Over 300 through 400 A3 AWG1 AWG
Over 400 through 500 A2 AWG1/0 AWG
Over 500 through 600 A1 AWG2/0 AWG
Over 600 through 800 A1/0 AWG3/0 AWG
Over 800 through 1000 A2/0 AWG4/0 AWG
Over 1000 through 1200 A3/0 AWG250 kcmil
Over 1200 through 1600 A4/0 AWG350 kcmil
Over 1600 through 2000 A250 kcmil400 kcmil
Over 2000 through 2500 A350 kcmil600 kcmil
Over 2500 through 3000 A400 kcmil600 kcmil
Over 3000 through 4000 A500 kcmil750 kcmil
Over 4000 through 5000 A700 kcmil1250 kcmil
Over 5000 through 6000 A800 kcmil1250 kcmil

Above 6000A, Table 250.122 no longer applies directly — NEC 250.122(A) instead requires the EGC to be at least 12.5% of the circular-mil area of the largest ungrounded conductor.

The 250.122(B) Proportional Increase

When ungrounded conductors are increased in size for voltage drop (or any reason other than ambient temperature correction or more than 3 current-carrying conductors), a wire-type EGC run with them must be increased in circular-mil area by the same proportion.

StepWhat to DoNotes
1Find the minimum required ungrounded conductor sizeFrom an NEC Table 310.16 ampacity calculation for the actual load, insulation rating, and installation conditions
2Find the actual installed ungrounded conductor sizeThe larger size actually being installed, typically to control voltage drop over a long run
3Calculate the circular-mil-area ratioActual installed conductor CM ÷ minimum required conductor CM
4Scale the table-derived EGC size by that ratioTable 250.122 EGC size CM × ratio from step 3
5Round up to the next standard sizeNever round down, and never leave the result at a non-standard value
6Cap at the ungrounded conductor's own sizeThe EGC is never required to be larger than the ungrounded conductor it runs with

Worked Example — 100A Feeder Upsized for Voltage Drop

100A Copper Feeder, Ungrounded Conductors Upsized From 8 AWG to 6 AWG

Illustrative example

StepCalculationResult
Table 250.122 lookup100A OCPD → copper column8 AWG copper
Minimum required ungrounded sizeFrom ampacity calculation8 AWG (16,510 CM)
Actual installed ungrounded sizeUpsized for voltage drop6 AWG (26,240 CM)
Proportional ratio26,240 ÷ 16,510≈ 1.59×
Final required EGC size8 AWG (16,510 CM) × 1.59 ≈ 26,250 CM → next standard size up6 AWG copper

Without the 250.122(B) check, a plain OCPD-rating lookup alone would have suggested the smaller 8 AWG EGC size — technically undersized relative to the actual upsized ungrounded conductors, even though the OCPD rating itself never changed.

Common Mistakes

Sizing the EGC From Conductor Ampacity Instead of the OCPD Rating

Table 250.122 keys strictly off the rating of the overcurrent device protecting the circuit — not the ampacity of the circuit's own conductors, which is frequently a different number.

Forgetting the 250.122(B) Check After a Voltage-Drop Upsize

Upsizing ungrounded conductors for voltage drop is common on long runs, but the resulting need to proportionally upsize the EGC is easy to overlook — leaving a technically undersized EGC even though the plain OCPD-rating lookup looks compliant.

Confusing the EGC With the Grounding Electrode Conductor

These are two different conductors, sized from two different tables (250.122 vs. 250.66), serving two different purposes. Using this calculator's result to size a grounding electrode conductor — or vice versa — produces the wrong answer for either.

Dividing the EGC Size Across Parallel Raceways

Where circuit conductors run in parallel across multiple raceways, each raceway needs its own full-size EGC based on the circuit's total OCPD rating — the EGC size is not divided among the raceways the way current is.

Applying an Outdated Table Value for Large Aluminum Services

The 2020 NEC revised the 5000A/6000A aluminum EGC row from 1200 kcmil to 1250 kcmil — several older or unverified 'wire size chart' sources still publish the outdated figure.

Relevant Standards and References

Equipment/protective grounding conductor sizing is code-specific — the underlying safety principle is universal, but the exact published tables and rules vary by code and edition.

RegionRelevant Codes / Guidance
United StatesNEC (National Electrical Code) Table 250.122 for EGC sizing, 250.122(B) for the proportional-increase rule, 250.118 for qualifying raceway-as-EGC methods
Europe / UKBS 7671 (IET Wiring Regulations) sizes the circuit protective conductor from its own separate table, commonly as a ratio to the phase conductor's cross-sectional area — structured differently from the NEC's OCPD-rating-based approach
General guidanceEquipment/protective grounding conductor sizing rules are code-specific and vary by edition — always confirm against the exact table and edition your local authority has adopted before finalizing a real installation.

Final Verdict

Correct EGC sizing is an OCPD-rating table lookup followed by a voltage-drop upsize check — skipping the second step is the single most common way an EGC ends up technically undersized on an otherwise fully code-compliant circuit.

  • Start from NEC Table 250.122 using the circuit's actual OCPD (breaker/fuse) rating, not the conductor's ampacity.
  • Check whether the ungrounded conductors were upsized for voltage drop or a similar reason — if so, apply the 250.122(B) proportional increase.
  • Round the proportional result up to the next standard size, and never size the EGC larger than the ungrounded conductor itself.
  • Confirm whether a wire-type EGC is actually needed, or whether the raceway itself qualifies as the EGC per NEC 250.118.
  • For parallel conductor runs, size each raceway's own full EGC from the full circuit OCPD rating — it isn't divided.
  • Never substitute this sizing for grounding electrode conductor (Table 250.66) sizing — they're different conductors for different purposes.

Related calculators

Use these calculators when you need to turn this reference information into project quantities:

Related resources

  • Grounding Electrode Conductor Sizing Guide

    Complete guide to sizing a grounding electrode conductor (GEC) — how NEC Table 250.66 works, the three electrode-specific size caps, copper vs. aluminum, and a worked example.

  • Wire Gauge Selection Guide

    Complete guide to selecting the correct wire gauge (AWG) — base ampacity by insulation rating, the derating factors that reduce it (conductor count, ambient temperature), the small-conductor breaker cap, and a worked example.

FAQ

The rating or setting of the automatic overcurrent device (breaker or fuse) protecting the circuit ahead of the equipment — not the ampacity of the circuit's own ungrounded conductors, and not the connected load in isolation. NEC Table 250.122 maps a range of OCPD ratings to a required EGC size, separately for copper and aluminum/copper-clad aluminum conductors.
Because the EGC's job is fundamentally different — it doesn't carry load current under normal operation, it carries fault current for a brief period until the overcurrent device trips. The overcurrent device's rating (not the conductor's ampacity) is what actually determines how much fault current the EGC needs to be able to briefly withstand, so that's the value Table 250.122 keys off.