20A Equipment Grounding Conductor Size Calculator (NEC Table 250.122)

Size the EGC for a 20A circuit.

Inputs

ℹ️The equipment grounding conductor's own material — not necessarily the same as the circuit's ungrounded conductors. Table 250.122 uses genuinely different size boundaries for copper and aluminum — aluminum EGCs run one to two sizes larger than the equivalent copper size.

A

ℹ️The rating or setting of the automatic overcurrent device (breaker or fuse) protecting the circuit ahead of the equipment — not the ampacity of the circuit conductors themselves. Common standard sizes: 15, 20, 30, 40, 60, 100, 150, 200, 400A, up to 6000A for large services — an adjustable-trip breaker's actual setting (e.g. 201A) works too, since Table 250.122 keys off the OCPD's "rating or setting," not just standard sizes.

Ungrounded Conductors Upsized?

Increased for Voltage Drop or Another Reason?

Cost

Enable Cost Estimation?

Required Equipment Grounding Conductor: 12 AWG (Copper)

Sized directly from NEC Table 250.122, no proportional increase applies

NEC Table 250.122 Lookup

OCPD (breaker/fuse) rating: 20 A

Table row: Over 15 through 20 A

Table-derived EGC size: 12 AWG

250.122(B) Upsize Check

Not checked — enable the upsize toggle if ungrounded conductors were increased for voltage drop or another reason

Assumptions Used

NEC Table 250.122 (minimum size equipment grounding conductors), NEC 250.122(B) proportional increase where ungrounded conductors are upsized. Assumes a single, homogeneous conductor material for both the ungrounded conductors and the EGC, and a single (non-parallel) raceway or cable run. This is a reference estimate — confirm against the code edition adopted in your jurisdiction and a licensed electrician before final installation.

Want the full walkthrough on Table 250.122, the 250.122(B) upsize rule, and how this differs from grounding electrode conductor sizing? Equipment Grounding Conductor Sizing Guide →

Equipment Grounding ConductorPanel20 AUngrounded conductor (OCPD-protected)12 AWGEquipmentFault current returns via the EGC — not through earthDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Equipment Grounding Conductor Size Calculator.

EGC sizing for a 20A branch circuit

A 20A breaker or fuse is one of the most common branch-circuit ratings in residential and light-commercial work — typical for kitchen small-appliance circuits, bathroom receptacles, and general 120V outlet circuits.

This page is pre-set to a 20A circuit with a copper EGC — edit the inputs above to match your actual OCPD rating and EGC material.

  • A 20A circuit needs a 12 AWG copper EGC per Table 250.122's '15A or less / over 15 through 20A' rows.
  • Switch EGC material to aluminum above to see the equivalent aluminum-column result.
  • If the ungrounded conductors were upsized beyond 12 AWG for voltage drop on a long run, enable the upsize toggle to check whether the EGC needs to scale up too.

Equipment Grounding Conductor Formula: How Is the Size Determined?

Two steps: a direct NEC Table 250.122 lookup from the OCPD rating, then a 250.122(B) proportional-increase check.

Step 1 — Table 250.122 Lookup

Find the Table 250.122 row whose OCPD-rating range contains the circuit's breaker/fuse rating

Table EGC Size = that row's EGC size, for the selected material (Cu or Al)

Table 250.122 has 19 rows, each covering a range of overcurrent device ratings, with separate copper and aluminum/copper-clad aluminum columns — sized from the OCPD rating, not the ampacity of the circuit conductors themselves.

Step 2 — 250.122(B) Proportional Increase

If ungrounded conductors were increased for voltage drop (or another reason besides temperature/conductor-count derating):

Ratio = Actual Installed Ungrounded Conductor CM ÷ Minimum Required Ungrounded Conductor CM

Final EGC = next standard size ≥ (Table EGC Size CM × Ratio), never larger than the ungrounded conductor itself

A 2020+ NEC exception also permits a qualified person to determine an alternative EGC size using engineering judgment instead of the strict circular-mil proportion — that professional-judgment path isn't modeled here, since it depends on site-specific analysis this calculator can't perform.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
OCPD rating20 ASets the Table 250.122 row
EGC materialCopperSets the Table 250.122 column
Ungrounded conductors upsized?NoDetermines whether the 250.122(B) proportional increase applies

Step 1 — Table 250.122 Lookup

CalculationResult
Table rowOver 15 through 20 A
Table-derived EGC size12 AWG

Step 2 — 250.122(B) Upsize Check

CalculationResult
Upsize checkNot checked — ungrounded conductors not marked as upsized
Final recommended size12 AWG (copper)

Therefore, for a 20 A circuit, you need approximately 12 AWG copper for the equipment grounding conductor.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

Per Table 250.122, a 20A OCPD needs a 12 AWG copper EGC (or 10 AWG aluminum), before any 250.122(B) proportional increase.
Only if the ungrounded conductors weren't upsized beyond what's normally required for voltage drop or another reason — if they were, enable the upsize toggle above to check whether the EGC needs to scale up proportionally.