MCA & MOCP Verification Checklist

Essential Checklist+

Complete these critical checks before approving the work or proceeding to the next construction stage.

βœ“14 Inspection Points
βœ“4 Verification Categories
βœ“Equipment & Input Data+
  • Nameplate MCA/MOCP read directly from the actual installed equipment, not estimated
  • Largest motor correctly identified before applying the 125%/175%/225% factors
  • Other motor and non-motor loads correctly summed from all components sharing the circuit
  • Wire material confirmed as copper or aluminum, matching the actual installed conductor
  • Local code edition and any local amendments confirmed before finalizing
βœ“MCA / MOCP Calculation+
  • MCA's 125% factor applied only to the largest motor, other loads added at 100%
  • MOCP rounding interpretation confirmed with a licensed electrician or AHJ, never exceeding the 225% ceiling
βœ“Wire & Breaker Selection+
  • Selected wire's (derated) ampacity confirmed to meet or exceed the MCA
  • Selected breaker/fuse size confirmed not to exceed the MOCP
  • Lower of the wire's insulation rating and the terminal/equipment rating used to select the ampacity column
βœ“Installation & Code Compliance+
  • Equipment grounding conductor sized separately, per NEC Table 250.122, not assumed from the MCA wire size
  • Equipment voltage and phase rating confirmed to match the actual supply before energizing
  • Permit and inspection requirements confirmed for the scope of HVAC electrical work
  • HVAC circuit work reviewed or performed by a licensed electrician or HVAC contractor
Full QC Checklist+

Verify equipment/input data, MCA/MOCP calculation, wire/breaker selection, and installation/code compliance.

βœ“20 Inspection Points
βœ“4 Verification Categories
βœ“Equipment & Input Data+
  • Nameplate MCA/MOCP read directly from the actual installed equipment, not estimated
  • Largest motor correctly identified before applying the 125%/175%/225% factors
  • Other motor and non-motor loads correctly summed from all components sharing the circuit
  • Wire material confirmed as copper or aluminum, matching the actual installed conductor
  • Local code edition and any local amendments confirmed before finalizing
βœ“MCA / MOCP Calculation+
  • MCA's 125% factor applied only to the largest motor, other loads added at 100%
  • MOCP rounding interpretation confirmed with a licensed electrician or AHJ, never exceeding the 225% ceiling
  • Final MOCP value confirmed as an actual standard NEC 240.6(A) ampere rating
  • From-scratch component-ratings calculation used only when no combined nameplate value exists
  • Calculated MOCP confirmed to actually let the motor start reliably, or the qualified-person exception documented
βœ“Wire & Breaker Selection+
  • Selected wire's (derated) ampacity confirmed to meet or exceed the MCA
  • Selected breaker/fuse size confirmed not to exceed the MOCP
  • Lower of the wire's insulation rating and the terminal/equipment rating used to select the ampacity column
  • Ambient-temperature and conductor-count derating applied for hot attics, rooftops, or shared conduits
  • Equipment disconnect switch sized and located separately, per NEC 440.14
βœ“Installation & Code Compliance+
  • Equipment grounding conductor sized separately, per NEC Table 250.122, not assumed from the MCA wire size
  • Outdoor-rated conductors, connectors, and disconnect enclosure used for outdoor condenser/compressor units
  • Equipment voltage and phase rating confirmed to match the actual supply before energizing
  • Permit and inspection requirements confirmed for the scope of HVAC electrical work
  • HVAC circuit work reviewed or performed by a licensed electrician or HVAC contractor
Inspection Notes+
Use the latest approved drawings, specifications, and site measurements.
Complete all critical checks before proceeding to the next work stage.
Record deviations and confirm rectification where required.