Equipment Grounding Conductor Size Verification Checklist

Essential Checklist+

Complete these critical checks before approving the work or proceeding to the next construction stage.

βœ“12 Inspection Points
βœ“4 Verification Categories
βœ“Circuit & System Inputs+
  • OCPD (breaker/fuse) rating confirmed from the actual installed device, not assumed from wire size
  • EGC material confirmed as copper or aluminum, matching the actual installed conductor
  • Low-impedance fault-current path confirmed end-to-end, back to the source
  • Local code edition and any local amendments confirmed before finalizing
βœ“250.122(B) Upsize Check+
  • Upsize reason confirmed as voltage drop or similar β€” not ambient temperature or conductor-count derating
  • Minimum required ungrounded conductor size correctly determined from ampacity tables, not guessed
  • Actual installed ungrounded conductor size confirmed from the panel schedule or as-built drawings
βœ“Table 250.122 Application+
  • Correct Table 250.122 row read for the actual OCPD rating and material
  • EGC sized from the OCPD rating, confirmed not to have been sized from conductor ampacity instead
βœ“Installation & Code Compliance+
  • Where a raceway itself serves as the EGC, its physical continuity and listing confirmed end-to-end
  • Permit and inspection requirements confirmed for the scope of circuit/equipment work
  • Circuit/equipment grounding work reviewed or performed by a licensed electrician
Full QC Checklist+

Verify circuit/system inputs, the 250.122(B) upsize check, Table 250.122 application, and installation/code compliance.

βœ“20 Inspection Points
βœ“4 Verification Categories
βœ“Circuit & System Inputs+
  • OCPD (breaker/fuse) rating confirmed from the actual installed device, not assumed from wire size
  • EGC material confirmed as copper or aluminum, matching the actual installed conductor
  • Wire-type EGC vs. raceway-as-EGC method confirmed for the actual installation
  • Low-impedance fault-current path confirmed end-to-end, back to the source
  • Local code edition and any local amendments confirmed before finalizing
βœ“250.122(B) Upsize Check+
  • Upsize reason confirmed as voltage drop or similar β€” not ambient temperature or conductor-count derating
  • Minimum required ungrounded conductor size correctly determined from ampacity tables, not guessed
  • Actual installed ungrounded conductor size confirmed from the panel schedule or as-built drawings
  • Proportional increase rounded up to the next standard conductor size, not left at a non-standard value
  • Final EGC size confirmed not larger than the ungrounded conductor it runs with
βœ“Table 250.122 Application+
  • Correct Table 250.122 row read for the actual OCPD rating and material
  • EGC sized from the OCPD rating, confirmed not to have been sized from conductor ampacity instead
  • Each parallel raceway confirmed to carry its own full-size EGC, not a divided fraction
  • For OCPD ratings above 6000A, the 12.5%-of-largest-ungrounded-conductor rule applied instead of Table 250.122
  • Terminal and lug ratings confirmed compatible with the final EGC size and material after any upsize
βœ“Installation & Code Compliance+
  • EGC connections and splices made with a listed connector or an irreversible method
  • Equipment bonding jumper sized correctly where used, matching or exceeding the circuit EGC
  • Where a raceway itself serves as the EGC, its physical continuity and listing confirmed end-to-end
  • Permit and inspection requirements confirmed for the scope of circuit/equipment work
  • Circuit/equipment grounding work reviewed or performed by a licensed electrician
Inspection Notes+
Use the latest approved drawings, specifications, and site measurements.
Complete all critical checks before proceeding to the next work stage.
Record deviations and confirm rectification where required.