TryBuildCalc

Refrigerator Backup Power Calculator (Keep Your Fridge Running During an Outage)

Size backup power for your refrigerator.

Inputs

What do you want to know?

Equipment to Power

Pick a preset for a typical starting point, or choose Custom and enter your equipment's actual nameplate watts.

Equipment 1

W

Battery Configuration

ℹ️Sets the default depth-of-discharge limit — override it below if your manufacturer specifies something different.

%

ℹ️Leave blank to use the selected battery type's recommended default.

V

ℹ️The voltage of ONE battery unit — commonly 6V, 12V, or 2V cells.

Ah
V

ℹ️Your inverter/UPS's DC bus voltage — must be an exact multiple of the single battery voltage above (e.g. 12V batteries build a 12/24/48V bank).

ℹ️How many battery strings you have (or plan to have) wired in parallel.

%

ℹ️Typically 80-90% — check your inverter/UPS's datasheet.

%

ℹ️A design safety margin so the system still performs adequately as the battery ages — not a claim about a battery's current condition.

Cost

Enable Cost Estimation?

Estimated Backup Runtime: 3.26 hours

From 100 Ah (1 × 100Ah battery/ies) at 150 W load

Load Breakdown

EquipmentWattsQty
Refrigerator150 W× 1
Total Load150 W

Battery Bank

Battery type: Sealed Lead-Acid / AGM / Gel (VRLA) (depth of discharge: 60%)

System voltage: 12V1 × 12V in series

Parallel strings: 1 × 100Ah = 100 Ah total

Total batteries needed: 1 (1 series × 1 parallel)

Efficiency: 85%, aging/end-of-life margin: 80%

Informational Inverter/UPS Sizing

Suggested inverter/UPS rating: 600 VA (assumes 0.8 power factor, 25% headroom)

Assumptions Used

Assumes a sustained/continuous load — motor-driven appliances (like a refrigerator's compressor) cycle on and off, so actual runtime for such loads can vary from this estimate. This is a reference estimate — confirm with a licensed electrician for a permanent installation.

Need longer, whole-house backup instead of a battery bank? Generator Size Calculator →

Sizing your dwelling's full electrical service? Panel Size Calculator →

UPS Battery Backup VisualizationBattery Bank1 × 100AhLoad150 WBackup Runtime3.26 hrsDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete UPS / Inverter Battery Capacity Calculator.

Refrigerator backup power sizing

A refrigerator's compressor cycles on and off rather than running continuously, so this calculator's estimate (using its rated watts as a steady load) is a reasonable planning figure, with real-world runtime often somewhat longer.

Edit the battery specs above to see how backup time changes with a larger battery bank.

  • A well-insulated, unopened refrigerator can also stay cold for several hours with no power at all — battery backup extends this further.
  • Add a second battery in parallel to roughly double the calculated runtime.
  • Consider adding a freezer or other essential loads to this list if you want them backed up together.

UPS Battery Formula: How Is Capacity Calculated?

The core formula is the same in both directions — only which variable you're solving for changes.

Step 1 — Total Load

Total Load (W) = Sum of every equipment row's Watts × Quantity

This is the total connected load you want backed up, treated as a sustained/continuous draw.

Step 2 — Usable Energy

Usable Energy (Wh) = Battery Ah × System Voltage × Depth of Discharge × Aging Factor × Efficiency

Depth of discharge, an aging/end-of-life margin, and inverter conversion efficiency all reduce how much of the battery's rated capacity actually reaches your equipment.

Step 3a — Runtime Mode

Runtime (hours) = Usable Energy ÷ Total Load

Given a battery bank's Ah and voltage, solve directly for how long it backs up your load.

Step 3b — Sizing Mode

Required Ah = (Total Load × Target Runtime) ÷ (System Voltage × Depth of Discharge × Aging Factor × Efficiency)

Batteries Needed = Series Count (for voltage) × Parallel Count (rounded up, for capacity)

Given a target runtime, solve backward for the required battery capacity, then round up to a whole number of batteries.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Equipment1 items, 150 W totalSets total load
BatterySealed Lead-Acid / AGM / Gel (VRLA), 60% DoDSets usable energy per Ah
ModeRuntime (given battery)Sets which variable is solved for

Steps 1-2 — Load and Usable Energy

CalculationResult
Total load150 W
Total battery capacity100 Ah
Usable energy490 Wh

Therefore, 100 Ah at 12V backs up 150 W of load for 3.26 hours.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

It depends on your specific refrigerator's rated watts and your battery's usable capacity — a typical refrigerator (around 150W) on a single 100Ah lead-acid battery commonly provides several hours; calculate your actual equipment for a precise figure.
No — the compressor cycles on and off, so actual average draw is lower than the rated watts while running. This calculator's estimate treats it as a steady load, a reasonable planning approximation that tends to be conservative (real backup time is often a bit longer).