EV Charger Load Calculator (NEC 625.41 — Wire & Breaker Sizing)

Calculate your EV charger circuit instantly.

Inputs

ℹ️Select your EVSE's charging level and amperage, or choose Custom to enter it directly.

A

ℹ️The EVSE's own nameplate rated continuous current — not the vehicle's onboard charger rating.

ℹ️Distance from the panel/breaker to the EVSE, one way — not round trip.

ℹ️The wire's own insulation rating (check the product's markings, e.g. THHN, THWN-2).

ℹ️Per NEC 110.14(C) — the breaker/panel/EVSE's own temperature rating. The calculator uses the lower of this and the insulation rating above.

Connection & Location

ℹ️Affects GFCI protection requirements per NEC 625.54.

Advanced (NEC Derating)

Adjust for Conductor Count / Ambient Temperature?

Cost

Enable Cost Estimation?

Recommended Circuit: 60A breaker, 6 AWG copper

For a 48.0A (11.5 kW) charger at 240V — sized by ampacity, not voltage drop

Ampacity Check

Design current: 60.0 A (125% continuous factor, NEC 625.41)

Minimum size by ampacity: 6 AWG

Derating factor applied: 1.00×

Final wire's derated ampacity: 65.0 A

Voltage Drop Check

Charger rated current: 48.0 A

Minimum size by voltage drop: 10 AWG

Allowed drop: 3.0%

Final wire's actual drop: 0.98% (2.36 V)

Circuit Summary

System240 V, single-phase
One-way run length50.0 ft (15.2 m)
Connection / locationHardwired, indoor

Panel Impact (Informational)

Service Size% of Service Used by This Circuit
100A60.0%
125A48.0%
150A40.0%
200A30.0%
225A26.7%

This is a single circuit's share of a service, not a full load calculation — use the Panel Size Calculator to check your service has capacity for this plus everything else.

Assumptions Used

NEC 625.41 (125% continuous-load factor), NEC Table 310.16 ampacity, NEC 110.14(C) governing rating, NEC 240.4(D) small-conductor cap. Assumes a dedicated branch circuit (NEC 625.42) — not a shared/EMS-managed circuit. This is a reference estimate — confirm with a licensed electrician before installation.

Checking your panel has enough total capacity for this plus everything else? Panel Size Calculator →

Need to size the conduit for this and other conductors? Conduit Fill Calculator →

EV Charger Circuit60APanel6 AWGEV11.5 kWEVSE / ChargerDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete EV Charger Load Calculator.

General EV charger circuit estimate

This page gives the full combined result — design current, wire size, breaker size, GFCI requirement, and panel impact — from one set of charger and installation inputs.

It's the same calculator behind every other EV-charging variant on this site, just without a specific scenario pre-selected — useful for a general check before finalizing your actual charger and installation.

  • Applies the NEC 625.41 125% continuous-load factor automatically.
  • Reuses the same ampacity, voltage drop, and breaker sizing engine as the Wire Size Calculator for guaranteed consistency.
  • Flags GFCI protection requirements by connection type and location.

EV Charger Circuit Formula: How Is It Calculated?

NEC 625.41's continuous-load treatment drives both the wire and breaker sizing.

Step 1 — Design Current

Design Current = Charger Rated Current × 1.25

Per NEC 625.41, EV charging equipment is always treated as a continuous load — this 125% factor applies regardless of how the charger is actually used.

Step 2 — Wire Size

Smallest AWG where: Derated Ampacity ≥ Design Current, AND

Voltage Drop at Charger Current ≤ Max Allowed %

The wire must satisfy both the design-current ampacity requirement and the voltage drop limit over the actual run length — whichever requires the larger wire governs.

Step 3 — Breaker Size

Recommended Breaker = smallest standard size ≥ Design Current

(capped by the wire's small-conductor OCPD limit, if lower)

Rounded up to a real NEC 240.6(A) standard breaker size, never a custom in-between value.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Charger48.0A at 240V (11.5 kW)Sets the base current before the continuous-load factor
Run Length50.0 ftSets the voltage drop check
Connection / LocationHardwired, indoorSets the GFCI requirement

Step 1 — Design Current

Calculation48.0 × 1.25
Design current60.0 A

Steps 2-3 — Wire and Breaker Size

CheckResult
Minimum size by ampacity (60.0A design current)6 AWG
Minimum size by voltage drop (3.0% max)10 AWG
Final wire (larger of the two)6 AWG
Breaker (design current rounded to standard size)60 A

Therefore, for a 48.0A charger at 240V, you need 60A breaker, 6 AWG copper.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

NEC 625.41's 125% continuous-load factor applied to your charger's rated current, then standard ampacity, voltage drop, and breaker sizing — the same engine as the Wire Size Calculator.
Yes — based on your connection type (receptacle vs. hardwired) and location (indoor vs. outdoor), per NEC 625.54.