TryBuildCalc

48 Amp EV Charger Breaker Size (NEC 625.41 — 60A Circuit)

Calculate your 48A charger breaker size.

Inputs

ℹ️Select your EVSE's charging level and amperage, or choose Custom to enter it directly.

A

ℹ️The EVSE's own nameplate rated continuous current — not the vehicle's onboard charger rating.

ℹ️Distance from the panel/breaker to the EVSE, one way — not round trip.

ℹ️The wire's own insulation rating (check the product's markings, e.g. THHN, THWN-2).

ℹ️Per NEC 110.14(C) — the breaker/panel/EVSE's own temperature rating. The calculator uses the lower of this and the insulation rating above.

Connection & Location

ℹ️Affects GFCI protection requirements per NEC 625.54.

Advanced (NEC Derating)

Adjust for Conductor Count / Ambient Temperature?

Cost

Enable Cost Estimation?

Recommended Circuit: 60A breaker, 6 AWG copper

For a 48.0A (11.5 kW) charger at 240V — sized by ampacity, not voltage drop

Ampacity Check

Design current: 60.0 A (125% continuous factor, NEC 625.41)

Minimum size by ampacity: 6 AWG

Derating factor applied: 1.00×

Final wire's derated ampacity: 65.0 A

Voltage Drop Check

Charger rated current: 48.0 A

Minimum size by voltage drop: 10 AWG

Allowed drop: 3.0%

Final wire's actual drop: 0.98% (2.36 V)

Circuit Summary

System240 V, single-phase
One-way run length50.0 ft (15.2 m)
Connection / locationHardwired, indoor

Panel Impact (Informational)

Service Size% of Service Used by This Circuit
100A60.0%
125A48.0%
150A40.0%
200A30.0%
225A26.7%

This is a single circuit's share of a service, not a full load calculation — use the Panel Size Calculator to check your service has capacity for this plus everything else.

Assumptions Used

NEC 625.41 (125% continuous-load factor), NEC Table 310.16 ampacity, NEC 110.14(C) governing rating, NEC 240.4(D) small-conductor cap. Assumes a dedicated branch circuit (NEC 625.42) — not a shared/EMS-managed circuit. This is a reference estimate — confirm with a licensed electrician before installation.

Checking your panel has enough total capacity for this plus everything else? Panel Size Calculator →

Need to size the conduit for this and other conductors? Conduit Fill Calculator →

EV Charger Circuit60APanel6 AWGEV11.5 kWEVSE / ChargerDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete EV Charger Load Calculator.

48A EV charger breaker sizing

A 48A EV charger is one of the higher-amperage common Level 2 options, delivering roughly 11.5 kW — this page is pre-set to that exact scenario.

Per NEC 625.41, a 48A charger needs a 60A breaker (48 × 1.25 = 60A), the next standard size up.

  • 48A × 1.25 = 60A design current, requiring a 60A standard breaker.
  • 6 AWG copper is a common wire pairing for a 60A EV charger circuit on a typical residential run.
  • A 48A charger draws significant panel capacity — check your service has adequate remaining capacity using the Panel Size Calculator.

EV Charger Circuit Formula: How Is It Calculated?

NEC 625.41's continuous-load treatment drives both the wire and breaker sizing.

Step 1 — Design Current

Design Current = Charger Rated Current × 1.25

Per NEC 625.41, EV charging equipment is always treated as a continuous load — this 125% factor applies regardless of how the charger is actually used.

Step 2 — Wire Size

Smallest AWG where: Derated Ampacity ≥ Design Current, AND

Voltage Drop at Charger Current ≤ Max Allowed %

The wire must satisfy both the design-current ampacity requirement and the voltage drop limit over the actual run length — whichever requires the larger wire governs.

Step 3 — Breaker Size

Recommended Breaker = smallest standard size ≥ Design Current

(capped by the wire's small-conductor OCPD limit, if lower)

Rounded up to a real NEC 240.6(A) standard breaker size, never a custom in-between value.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Charger48.0A at 240V (11.5 kW)Sets the base current before the continuous-load factor
Run Length50.0 ftSets the voltage drop check
Connection / LocationHardwired, indoorSets the GFCI requirement

Step 1 — Design Current

Calculation48.0 × 1.25
Design current60.0 A

Steps 2-3 — Wire and Breaker Size

CheckResult
Minimum size by ampacity (60.0A design current)6 AWG
Minimum size by voltage drop (3.0% max)10 AWG
Final wire (larger of the two)6 AWG
Breaker (design current rounded to standard size)60 A

Therefore, for a 48.0A charger at 240V, you need 60A breaker, 6 AWG copper.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

60A — per NEC 625.41's 125% continuous-load factor (48 × 1.25 = 60A), rounded to the next standard breaker size.
Commonly 6 AWG copper for a typical residential run, though your specific run length and conditions can change this — calculate your actual installation for a precise figure.