Makeup Air Calculator for Gas Appliances (IFGC/NFPA 54 Sizing)

Size your mechanical space's makeup air instantly.

Inputs

Appliances in This Space

Add every gas appliance sharing this room/closet — furnace, water heater, boiler, etc.

Appliance 1

BTU/hr

Appliance 2

BTU/hr

Space Size

The room, closet, or alcove enclosing these appliances — used to check whether it's a "confined" space under IFGC.

Enter Space Size By
ft
ft
ft
Unusually Tight Construction?

Weatherstripped doors/windows, sealed sheathing, no fireplace/other natural draft — even an otherwise-unconfined space still needs dedicated outdoor air here.

Outdoor Opening Details

Used for the single-opening method and the louver/grille free-area adjustment.

Single-Opening Method Eligible?

Only valid when every appliance in the space has a draft hood (or is fan-assisted Category I) and meets its required clearances — check your specific appliance's installation manual.

ℹ️Sets the free-area percentage used to convert required free area into the actual gross opening size you need to cut.

Confined Space — Combustion Air Required

30 sq in

each opening, outdoor two-opening method (direct/vertical duct) — see all methods below

160 cu ft actual space volume vs. 6,000 cu ft required (50 cu ft per 1,000 BTU/hr of 120,000 BTU/hr combined input) — this space is CONFINED.

MethodFree Area (Each)Gross Area (Each)
Indoor, two openings (to adjacent indoor space, same story)120 sq in120 sq in
Outdoor, two openings — direct or vertical duct30 sq in30 sq in
Outdoor, two openings — horizontal duct60 sq in60 sq in
Outdoor, single openingN/A — enable single-opening eligibility above

The 100 sq in floor above applies to the indoor method only. Every opening also needs a minimum 3 in cross-sectional dimension — this calculator computes area only, so confirm your actual width/height meets that separately.

Alternatively, a mechanical combustion air supply delivering at least 42 CFM from outdoors (interlocked so appliances can't fire without it running) satisfies all of the above.

Appliance Load

Appliances: 2

Combined input: 120,000 BTU/hr

Opening Sizing

Louver/grille type: Unlouvered Opening (No Grille/Louver) (100% free area)

Mechanical supply alternative: 42 CFM

Combustion Air Opening SizingConfined-space check → two-opening free area → gross areaHIGH OPENINGLOW OPENINGAppliance(s)Confined Space160 cu ft actual vs. 6,000 cu ft requiredRequired Free Area30 sq inper opening, outdoor/vertical methodRequired Gross Area30 sq inafter louver/grille free area %Illustrative — not to scale. Verify against your specific room and appliance layout.

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Combustion & Makeup Air Sizing Calculator.

General-purpose makeup air sizing

This is the general-purpose entry point for combustion/makeup air sizing — add every gas appliance sharing your space and compare all four sizing methods side by side.

This page defaults to the classic worked example: an 80,000 BTU furnace plus a 40,000 BTU water heater sharing a small closet — edit the inputs above to match your actual appliances.

Combustion Air Formula: How Is It Determined?

Every method starts from the same combined Btu/hr input, then applies a different code-specified divisor and minimum.

Confined Space Check (Standard Method)

Required Volume (cu ft) = Combined Appliance Input (BTU/hr) ÷ 1,000 × 50

If your actual room/closet volume is less than this required volume, the space is "confined" and needs dedicated combustion air. At or above it, infiltration is normally adequate — unless the building is of unusually tight construction, which needs outdoor air regardless, sized using the same outdoor methods below (not a separate formula).

Two-Opening Methods (Indoor or Outdoor)

Indoor (to adjacent space, same story): 1 sq in per 1,000 BTU/hr, each opening

Outdoor, direct or vertical duct: 1 sq in per 4,000 BTU/hr, each opening

Outdoor, horizontal duct: 1 sq in per 2,000 BTU/hr, each opening

The indoor method's each opening also has its own 100 sq in floor — a small combined appliance load can compute to less than 100 sq in by the formula alone, but the code requires at least 100 sq in per opening regardless. This floor does NOT apply to either outdoor two-opening method. One opening goes within 12 in of the top of the enclosure, the other within 12 in of the bottom. A different, larger requirement applies to an indoor opening connecting a different story — not modeled here.

Outdoor Single-Opening Method

Free Area (sq in) = max(Combined Input ÷ 3,000, Total Vent Connector Area)

Only valid when every appliance has a draft hood (or is fan-assisted Category I) and meets its required clearances. The opening can never be smaller than the combined vent connector (draft-hood/flue-collar outlet) area of the appliances, even if the formula alone would allow it.

Gross (Actual Cut) Opening Size

Gross Area (sq in) = Free Area ÷ Louver/Grille Free Area %

Free area is the portion of an opening actually open to airflow — a louver or grille blocks some of it. Per IFGC 304.10's own default assumptions (when a specific product's free area isn't yet known): 100% for a bare unlouvered opening, 75% for a metal louver/grille, 25% for a wood louver.

Mechanical Combustion Air Supply (Alternative)

Required Supply (CFM) = Combined Appliance Input (BTU/hr) ÷ 1,000 × 0.35

Supplied from outdoors, with every served appliance interlocked to the supply fan so the main burner can't fire unless it's running. This replaces passive openings entirely where wall access is impractical.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValue
Combined appliance input120,000 BTU/hr (2 appliances)
Space volume160 cu ft
Louver/grille typeUnlouvered Opening (No Grille/Louver) (100%)

Step-by-Step Calculation

StepCalculationResult
Required volume (confined-space check)120000 ÷ 1,000 × 506,000 cu ft
Space status160 vs. 6,000 cu ftConfined
Outdoor two-opening, vertical (each)120000 ÷ 4,00030 sq in
Outdoor two-opening, horizontal (each)120000 ÷ 2,00060 sq in
Gross area, outdoor two-opening vertical (each)30 ÷ 100%30 sq in
Mechanical supply alternative120000 ÷ 1,000 × 0.3542 CFM

Therefore, 120,000 BTU/hr of combined appliance input in a 160 cu ft space is a confined space. Using the outdoor two-opening method with a direct or vertical duct, each opening needs at least 30 sq in of gross (actual cut) area — see the full method comparison above for the other options.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

In this context, yes — both terms describe outdoor (or adjacent indoor) air brought in to replace what a gas appliance consumes for combustion, keeping the appliance space from becoming depressurized or oxygen-deficient. (A separate, unrelated use of 'makeup air' covers replacing air exhausted by a kitchen range hood or whole-house fan — a different calculation this site handles on those calculators' own pages.)
Any atmospheric-draft or fan-assisted (non-direct-vent) gas appliance drawing combustion air from the room it's installed in — furnaces, boilers, and standard water heaters most commonly. Sealed-combustion (direct-vent) appliances draw air from outdoors through their own intake and don't count.