Confined Space Gas Appliance Calculator (50 Cu Ft Per 1,000 BTU/hr Check)

Check your space and size combustion air instantly.

Inputs

Appliances in This Space

Add every gas appliance sharing this room/closet — furnace, water heater, boiler, etc.

Appliance 1

BTU/hr

Space Size

The room, closet, or alcove enclosing these appliances — used to check whether it's a "confined" space under IFGC.

Enter Space Size By
cu ft
Unusually Tight Construction?

Weatherstripped doors/windows, sealed sheathing, no fireplace/other natural draft — even an otherwise-unconfined space still needs dedicated outdoor air here.

Outdoor Opening Details

Used for the single-opening method and the louver/grille free-area adjustment.

Single-Opening Method Eligible?

Only valid when every appliance in the space has a draft hood (or is fan-assisted Category I) and meets its required clearances — check your specific appliance's installation manual.

ℹ️Sets the free-area percentage used to convert required free area into the actual gross opening size you need to cut.

Confined Space — Combustion Air Required

20 sq in

each opening, outdoor two-opening method (direct/vertical duct) — see all methods below

500 cu ft actual space volume vs. 4,000 cu ft required (50 cu ft per 1,000 BTU/hr of 80,000 BTU/hr combined input) — this space is CONFINED.

MethodFree Area (Each)Gross Area (Each)
Indoor, two openings (to adjacent indoor space, same story)100 sq in100 sq in
Outdoor, two openings — direct or vertical duct20 sq in20 sq in
Outdoor, two openings — horizontal duct40 sq in40 sq in
Outdoor, single openingN/A — enable single-opening eligibility above

The 100 sq in floor above applies to the indoor method only. Every opening also needs a minimum 3 in cross-sectional dimension — this calculator computes area only, so confirm your actual width/height meets that separately.

Alternatively, a mechanical combustion air supply delivering at least 28 CFM from outdoors (interlocked so appliances can't fire without it running) satisfies all of the above.

Appliance Load

Appliances: 1

Combined input: 80,000 BTU/hr

Opening Sizing

Louver/grille type: Unlouvered Opening (No Grille/Louver) (100% free area)

Mechanical supply alternative: 28 CFM

Combustion Air Opening SizingConfined-space check → two-opening free area → gross areaHIGH OPENINGLOW OPENINGAppliance(s)Confined Space500 cu ft actual vs. 4,000 cu ft requiredRequired Free Area20 sq inper opening, outdoor/vertical methodRequired Gross Area20 sq inafter louver/grille free area %Illustrative — not to scale. Verify against your specific room and appliance layout.

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Combustion & Makeup Air Sizing Calculator.

Confined space check

This page defaults to the Room Volume entry mode, letting you check an already-known space volume directly against the 50 cu ft per 1,000 BTU/hr threshold without entering separate length/width/height dimensions.

This page defaults to an 80,000 BTU/hr furnace in a 500 cu ft space (just over the 4,000 cu ft an unconfined space would need) — edit the inputs above to match your actual appliance and space.

Combustion Air Formula: How Is It Determined?

Every method starts from the same combined Btu/hr input, then applies a different code-specified divisor and minimum.

Confined Space Check (Standard Method)

Required Volume (cu ft) = Combined Appliance Input (BTU/hr) ÷ 1,000 × 50

If your actual room/closet volume is less than this required volume, the space is "confined" and needs dedicated combustion air. At or above it, infiltration is normally adequate — unless the building is of unusually tight construction, which needs outdoor air regardless, sized using the same outdoor methods below (not a separate formula).

Two-Opening Methods (Indoor or Outdoor)

Indoor (to adjacent space, same story): 1 sq in per 1,000 BTU/hr, each opening

Outdoor, direct or vertical duct: 1 sq in per 4,000 BTU/hr, each opening

Outdoor, horizontal duct: 1 sq in per 2,000 BTU/hr, each opening

The indoor method's each opening also has its own 100 sq in floor — a small combined appliance load can compute to less than 100 sq in by the formula alone, but the code requires at least 100 sq in per opening regardless. This floor does NOT apply to either outdoor two-opening method. One opening goes within 12 in of the top of the enclosure, the other within 12 in of the bottom. A different, larger requirement applies to an indoor opening connecting a different story — not modeled here.

Outdoor Single-Opening Method

Free Area (sq in) = max(Combined Input ÷ 3,000, Total Vent Connector Area)

Only valid when every appliance has a draft hood (or is fan-assisted Category I) and meets its required clearances. The opening can never be smaller than the combined vent connector (draft-hood/flue-collar outlet) area of the appliances, even if the formula alone would allow it.

Gross (Actual Cut) Opening Size

Gross Area (sq in) = Free Area ÷ Louver/Grille Free Area %

Free area is the portion of an opening actually open to airflow — a louver or grille blocks some of it. Per IFGC 304.10's own default assumptions (when a specific product's free area isn't yet known): 100% for a bare unlouvered opening, 75% for a metal louver/grille, 25% for a wood louver.

Mechanical Combustion Air Supply (Alternative)

Required Supply (CFM) = Combined Appliance Input (BTU/hr) ÷ 1,000 × 0.35

Supplied from outdoors, with every served appliance interlocked to the supply fan so the main burner can't fire unless it's running. This replaces passive openings entirely where wall access is impractical.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValue
Combined appliance input80,000 BTU/hr (1 appliance)
Space volume500 cu ft
Louver/grille typeUnlouvered Opening (No Grille/Louver) (100%)

Step-by-Step Calculation

StepCalculationResult
Required volume (confined-space check)80000 ÷ 1,000 × 504,000 cu ft
Space status500 vs. 4,000 cu ftConfined
Outdoor two-opening, vertical (each)80000 ÷ 4,00020 sq in
Outdoor two-opening, horizontal (each)80000 ÷ 2,00040 sq in
Gross area, outdoor two-opening vertical (each)20 ÷ 100%20 sq in
Mechanical supply alternative80000 ÷ 1,000 × 0.3528 CFM

Therefore, 80,000 BTU/hr of combined appliance input in a 500 cu ft space is a confined space. Using the outdoor two-opening method with a direct or vertical duct, each opening needs at least 20 sq in of gross (actual cut) area — see the full method comparison above for the other options.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

By comparing your space's actual volume against 50 cubic feet per 1,000 BTU/hr of the COMBINED input of every appliance in it. Below that required volume, the space is confined and needs dedicated combustion air; at or above it, infiltration is normally adequate (unless the building is of unusually tight construction).
80,000 ÷ 1,000 x 50 = 4,000 cubic feet — a standard 8 ft ceiling room would need roughly 500 sq ft of floor area to reach that volume, which most dedicated furnace closets and small mechanical rooms fall well short of.