HVAC Refrigerant Types: R-410A vs R-32 vs R-454B

Residential air conditioners and heat pumps are in the middle of a refrigerant transition as significant as the R-22-to-R-410A switch two decades ago — new equipment manufactured from 2025 onward is required to use a lower-global-warming-potential refrigerant instead of R-410A, and understanding what changed (and what didn't) matters whether a system is being replaced, serviced, or just installed for the first time.

Last updated: September 28, 2026

Residential HVAC has gone through exactly one refrigerant transition of this scale before — R-22 to R-410A in the 2000s — and it's now in the middle of the next one. New central air conditioners, heat pumps, and mini-splits manufactured from 2025 onward are required to use a lower-global-warming-potential refrigerant instead of R-410A, and the two leading replacements, R-32 and R-454B, come with a different safety classification that changes how new equipment is installed and serviced.

This guide compares the refrigerants involved, explains what the phase-down does and doesn't require of existing equipment, and covers what to check before servicing new A2L-refrigerant systems.

Refrigerant Comparison

The table below compares the four refrigerants most relevant to residential HVAC today, from the phased-out R-22 to the current transition refrigerants.

RefrigerantTypeGWP (approx.)Ozone ImpactFlammability ClassCurrent Status
R-22HCFC~1,810Ozone-depleting (nonzero ODP)A1 (nonflammable)Production/import banned since Jan. 1, 2020; service-only via reclaimed/recycled stock
R-410AHFC blend~2,0880 (zero)A1 (nonflammable)Standard for ~2000s–2024 equipment; being phased down for new equipment under the AIM Act; still used to service existing systems
R-32HFC (single component)~6750 (zero)A2L (mildly flammable)Approved lower-GWP replacement adopted in new 2025+ model-year equipment
R-454BHFO/HFC blend~4660 (zero)A2L (mildly flammable)Most widely adopted R-410A replacement among major US manufacturers for new 2025+ equipment

GWP figures are commonly cited approximate values (100-year basis) — always confirm the exact figure and classification for a specific refrigerant blend from its official safety data sheet.

What This Means for You

The table below covers the most common situations homeowners and technicians run into during this transition.

Your SituationWhat to DoWhy
Have an existing central AC or heat pump running on R-410ANo action neededThe phase-down applies to new equipment manufacturing, not equipment already in service
Buying new central AC, heat pump, or mini-split equipment nowExpect R-32 or R-454B, not R-410ANew residential equipment is required to use a lower-GWP refrigerant as of the 2025 model year
Have an old R-22 system needing a major refrigerant-circuit repairBudget for full system replacement rather than an R-22 rechargeNew R-22 production/import ended in 2020; reclaimed supply is limited and increasingly costly
Installing or servicing new A2L (R-32/R-454B) equipmentUse a technician specifically trained and equipped for A2L refrigerantsDifferent handling, leak-detection, and code requirements apply versus R-410A
Comparing quoted equipment across different refrigerant typesCompare SEER2/HSPF2 ratings directly, not the refrigerant type itselfRefrigerant choice and rated efficiency are separate variables

Worked Example — Identifying a System's Refrigerant

Manufacture date is a useful clue, but the nameplate is the only reliable source — here's how to walk through it.

Example — Figuring Out Which Refrigerant a Specific System Uses

Two neighboring homes had central AC systems installed six years apart — one in 2019, one in 2025 — and want to know what refrigerant each one runs on before scheduling service.

StepBasisResult
2019-installed system: check the nameplate/data plate refrigerant labelManufactured before the 2025 phase-down cutoffVery likely R-410A — confirm on the nameplate
2025-installed system: check the nameplate/data plate refrigerant labelManufactured after the new-equipment GWP limit took effectLikely R-32 or R-454B — the exact type depends on the manufacturer, confirm on the nameplate
Booking a service call for either systemRefrigerant type determines required technician training/toolsConfirm the servicing technician is equipped for the specific refrigerant before the appointment

Manufacture date is a useful clue but not a guarantee — some equipment sold in a transition year may still carry pre-2025 production stock. The nameplate's refrigerant designation is the only reliable source.

Common Mistakes

Assuming an Existing R-410A System Must Be Replaced Because of the Phase-Down

The new-equipment GWP limit applies only to equipment manufactured from 2025 onward — a working R-410A system already installed can continue to be serviced and recharged with R-410A for the rest of its service life with no regulatory requirement to replace it early.

Attempting to Top Off or Retrofit an R-410A System with R-32 or R-454B

These refrigerants operate at different pressures, use different equipment safety designs for their A2L flammability classification, and are not approved drop-in substitutes for R-410A hardware — mixing refrigerant types or charging equipment with a refrigerant it wasn't listed for is unsafe and voids equipment listings.

Hiring a Technician Without A2L-Specific Training or Tools for New Refrigerant Systems

A2L refrigerants require leak-detection equipment calibrated for their flammability class and handling procedures beyond what standard R-410A (A1, nonflammable) service calls for. EPA Section 608 certification alone doesn't guarantee this — confirm the technician has specific A2L training and A2L-rated tooling in addition to holding the correct Section 608 certification type before booking service on 2025-or-later equipment.

Confusing a Lower-GWP Refrigerant Switch with an Efficiency Downgrade

GWP measures climate impact if refrigerant is released, not how efficiently the system uses electricity — R-32 and R-454B equipment lines are generally engineered to match or improve on the efficiency tiers their R-410A predecessors offered. Compare SEER2/HSPF2 directly rather than assuming the refrigerant change itself lowered efficiency.

Repeatedly Recharging a Failing R-22 System Instead of Budgeting for Replacement

With new R-22 production and import ended since 2020, reclaimed R-22 supply is limited and increasingly expensive, and a major leak or compressor failure on an R-22 system is now commonly more economical to address with full system replacement than with continued recharges of a shrinking refrigerant supply.

Standards and References

SourceWhat It Covers
EPA AIM Act (2020) and HFC phase-down rulesDirects the EPA's phase-down of high-GWP HFC refrigerant production/consumption, including the GWP limit for new residential AC/heat pump equipment effective January 1, 2025.
Montreal Protocol / Clean Air Act Title VIThe basis for R-22's ozone-depleting HCFC phase-out, with new US production and import ended as of January 1, 2020.
ASHRAE Standard 34Refrigerant safety classification system defining toxicity and flammability classes, including the A1 (nonflammable) and A2L (mildly flammable) classes referenced throughout this transition.
UL 60335-2-40Safety standard specific to air conditioning and heat pump equipment using A2L (mildly flammable) refrigerants.
EPA Section 608 technician certificationFederal refrigerant handling certification requirements for HVAC technicians (certification itself doesn't expire and has no separate A2L endorsement — A2L competency comes from additional manufacturer/industry training and A2L-rated tools alongside the correct Section 608 type).

Final Takeaway

Existing R-410A equipment isn't affected by the phase-down and can keep being serviced with R-410A for its full service life — the real-world impact is on new equipment, which now ships with R-32 or R-454B and needs technicians equipped and trained for their A2L mild-flammability classification.

  • New residential AC/heat pump equipment from the 2025 model year onward uses R-32 or R-454B, not R-410A, under the EPA's AIM Act phase-down.
  • Existing R-410A systems can continue to be serviced and recharged with R-410A — no regulatory requirement to replace them early.
  • R-32 and R-454B carry an A2L (mildly flammable) safety classification and are not drop-in substitutes for R-410A equipment.
  • R-22 production and import ended in 2020; a major repair on an R-22 system is usually more economical addressed by full replacement.
  • Refrigerant GWP and equipment efficiency (SEER2/HSPF2) are separate properties — compare ratings directly, don't assume a refrigerant switch changes efficiency.
  • Confirm a technician is specifically trained and equipped for A2L refrigerants before booking service on 2025-or-later equipment.

Related calculators

Use these calculators when you need to turn this reference information into project quantities:

Related resources

  • SEER vs SEER2 Ratings Explained

    Explains the difference between the old SEER rating and the current SEER2 (plus EER2 and HSPF2) ratings — the 2023 DOE test procedure change behind it, why SEER2 numbers run lower for the same equipment, and how regional minimum efficiency standards apply.

  • Heat Pump vs Gas Furnace: Which Is Best

    Head-to-head comparison of electric heat pumps and gas furnaces covering installed cost, running cost, efficiency (COP vs AFUE), cold-climate performance, balance point, backup heat, and dual-fuel hybrid systems.

FAQ

Equipment installed roughly from the mid-2000s through 2024 overwhelmingly uses R-410A, which itself replaced the older R-22 refrigerant over that same transition period. Starting with the 2025 model year, new residential air conditioners, heat pumps, and mini-splits are required to use a lower-global-warming-potential refrigerant instead of R-410A, and the two refrigerants that major US manufacturers have adopted most widely for this transition are R-454B and R-32. Which specific refrigerant a given new unit uses depends on the manufacturer — check the equipment's nameplate rather than assuming based on age alone.
R-410A has zero ozone depletion potential, which is why it replaced ozone-depleting R-22 in the first place, but it carries a high Global Warming Potential (GWP) — commonly cited around 2,088, meaning one pound of it traps roughly 2,088 times as much heat in the atmosphere as one pound of CO2 over a 100-year period if it leaks or is released. The concern driving the current phase-down is climate impact from leaked refrigerant, not ozone depletion, and it's addressed through the same kind of regulatory phase-down mechanism (in this case, the EPA's implementation of the AIM Act) that previously phased out ozone-depleting refrigerants like R-22.