Stair Stringer Rise & Run Code Guide

Stair code compliance comes down to a handful of numbers — maximum riser height, minimum tread depth, and how much those numbers are allowed to vary within one flight — plus a separate, less-discussed set of rules for how far apart and how far a stringer itself is allowed to span.

Last updated: September 6, 2026

Stair code compliance is mostly arithmetic — a fixed total rise and total run have to be divided into steps that stay under a maximum riser height, at or over a minimum tread depth, and consistent with each other within a tight tolerance. Get the division wrong and a stringer that looks fine on the shop floor fails inspection.

This guide covers the IRC riser and tread numbers, the separate rules for how far apart and how far a stringer can span, and the rise/run mistakes that most commonly show up on a first stair build.

Cut vs. Solid Stringers at a Glance

Stringer TypeMax Horizontal SpanSpacingThickness
Cut (open) stringer6 ft maximum horizontal spanTypically ≤18" O.C. (tighter often used for heavy-use stairs)2x12, minimum 5" throat remaining after notching
Solid (closed) stringerUp to ~13'-3" span (2-stringer stairway, ≤36" wide)Typically 2 stringers total, positioned at tread ends2x12, full un-notched depth retained

A solid stringer's much longer span allowance only applies to a genuinely un-notched board in a 2-stringer, ≤36"-wide configuration — it isn't a substitute rule for a cut stringer of the same lumber size.

Riser, Tread, and Nosing Code Numbers

These are the numbers most stair inspections check first, and the ones most commonly missed on a first layout:

  • Maximum riser height: 7-3/4", measured vertically between consecutive tread nosings.
  • Minimum tread depth: 10", measured horizontally, nosing to nosing.
  • Maximum riser-to-riser (and tread-to-tread) variance within one flight: 3/8".
  • Nosing projection, where present: 3/4" to 1-1/4", with a maximum nosing radius of 9/16" to limit trip hazard.

Worked Example — Solving Rise and Run Together

9 ft (108") Total Rise

Illustrative example

StepCalculationResult
Minimum risers needed108" ÷ 7.75" = 13.94Round up to 14 risers
Actual riser height108" ÷ 147.71" per riser
Treads (one fewer than risers)14 risers − 113 treads, 10" each minimum

Rounding the riser count UP (never down) is what keeps the resulting riser height under the 7-3/4" maximum — rounding down here would produce a 108" ÷ 13 = 8.31" riser, well over the limit.

Common Mistakes

Dividing Total Rise by Too Few Risers

Using fewer, taller risers to reduce step count pushes individual riser height over the 7-3/4" maximum — always divide total rise by enough risers to keep every one at or under the limit, then check the resulting tread depth still clears 10" minimum.

Ignoring the Riser/Tread Uniformity Rule

Every riser (and separately, every tread) in a flight must stay within 3/8" of the others — a flight with mostly-uniform steps and one adjusted riser at the top or bottom to make the numbers work fails this rule even if every individual riser is under the 7-3/4" cap.

Exceeding the Cut Stringer's 6 ft Span Without Adding Support

A cut stringer notched down to its minimum throat has meaningfully less structural depth than an un-notched board of the same size, and is limited to a 6 ft unsupported span as a result — running a longer flight on cut stringers without a mid-span landing or extra support is a common structural oversight.

Applying Solid Stringer Span Rules to a Cut Stringer Layout

The extended ~13'-3" span allowance applies specifically to solid, un-notched stringers in a 2-stringer, ≤36"-wide configuration — it doesn't carry over to a cut (notched) stringer just because the lumber size matches; the two stringer types have separate, non-interchangeable span limits.

Not Verifying Local Code Adoption and Edition

Stair rise, run, and stringer figures are published by code (in the US, the IRC) and states/jurisdictions frequently apply their own amendments to these exact numbers — confirm the specific table and edition in force locally before finalizing a real stringer.

Relevant Standards and References

Riser/tread requirements are code-specific, and stairs are one of the areas most frequently adjusted by state or local amendment — the underlying safety logic (consistent, non-excessive steps) is universal, but the exact numbers vary.

RegionRelevant Codes / Guidance
United StatesIRC Section R311.7 covers maximum riser height, minimum tread depth, riser/tread uniformity, and nosing requirements for residential stairs
Europe / UKUK Building Regulations Approved Document K covers private stair pitch, going (tread depth), and rise requirements; equivalent national regulations apply elsewhere in Europe alongside Eurocode 5 for structural timber design
IndiaThe National Building Code of India covers general means-of-egress and stair requirements; specific riser/tread numbers are less uniformly codified for single-family residential stairs than in the IRC
Australia / New ZealandThe National Construction Code (NCC) Volume Two, Part H1D7 covers residential (Class 1) stair riser and going dimensions, including the 2R + G formula (twice the riser plus the going, generally 550–700 mm)
General guidanceRiser/tread numbers and stringer span limits are code- and edition-specific, and states or councils frequently apply their own amendments — always confirm the exact table and edition your local authority has adopted before cutting a real stringer.

Final Verdict

Stair rise and run compliance comes down to rounding riser count up (never down), checking that every riser and tread stays within the uniformity tolerance, and matching the stringer type to the span it's actually being asked to cover.

  • Round the riser count UP when dividing total rise — never down — to keep every riser at or under 7-3/4".
  • Confirm every individual tread still clears the 10" minimum after solving for riser count.
  • Check riser-to-riser and tread-to-tread variance stays within 3/8" across the whole flight, not just the average.
  • Match stringer type to span: 6 ft max for cut stringers, up to ~13'-3" for a 2-stringer solid layout under 36" wide.
  • Don't apply solid-stringer span allowances to a cut (notched) stringer of the same lumber size.
  • Confirm the exact table and code edition — and any state/local amendments — your jurisdiction has adopted before cutting a real stringer.

Related calculators

Use these calculators when you need to turn this reference information into project quantities:

Related resources

  • Stud Spacing Guide (16" vs 24" O.C.)

    Complete guide to wall stud spacing — when 16 inch on-center is required, when 24 inch is allowed, how spacing interacts with stud size and wall height, and the material/insulation trade-offs of each.

  • Rafter vs. Truss: Which Should You Use?

    A practical comparison of stick-built rafters and prefabricated roof trusses — cost per square foot, achievable span, usable attic space, installation speed, and design flexibility — to help decide which fits a given roof.

  • Floor Joist Span & Spacing Guide

    How floor joist span, spacing, lumber size, species, and grade relate to each other — reading a span table correctly, the living-area vs. sleeping-room load difference, and the spacing/size trade-off.

  • Rafter Span & Sizing Guide

    How rafter span, spacing, roof pitch, and ground snow load relate to each other — reading a rafter span table correctly, why snow load can cut allowable span dramatically, and how pitch changes the load a rafter actually sees.

FAQ

Under the IRC, the maximum riser height is 7-3/4 inches, measured as the vertical distance between the nosings (or surfaces) of two consecutive treads. This is the number that most often gets violated on DIY stair builds, typically by dividing total rise by too few steps and ending up with a riser that's slightly over the limit — always divide rise by enough risers to keep every one of them at or under 7-3/4", not just close to it.
Minimum tread depth under the IRC is 10 inches, measured horizontally from nosing to nosing (or from the leading edge of one tread to the leading edge of the next). Tread depth and riser height are usually solved together, since a fixed total run and total rise constrain both — shrinking risers to stay under 7-3/4" while keeping every tread at or above 10" is the actual design problem a stringer layout has to solve.