TryBuildCalc

Window/Portable AC BTU Calculator (Room Air Conditioner Sizing)

Size your window or portable air conditioner instantly.

Inputs

Unit Type
Calculation Mode
ft²

ℹ️Measured floor area of the single, enclosed room this unit will cool — not a multi-room open floor plan.

ft

ℹ️Energy Star's sizing chart assumes an 8 ft ceiling. Taller rooms hold more air and may need a larger unit than shown.

ℹ️Very sunny rooms need +10% capacity; heavily shaded rooms need 10% less, per Energy Star's guidance.

Is This a Kitchen?

ℹ️Adds 600 BTU for each person beyond a baseline of 2 who regularly uses this room.

Recommended Capacity

7,000 BTU/hr

Match against the unit's nameplate/CEER BTU rating

Room & Conditions

Unit type: Window / Through-the-Wall

Room area: 300 sq ft

Sun exposure: Average / Typical

Kitchen: No

Occupants: 2

Sizing Breakdown

Base capacity (area only): 7,000 BTU/hr

After adjustments: 7,000 BTU/hr

Recommended nominal size: 7,000 BTU/hr

Window / Wall Air ConditionerRoom area → adjustments → recommended BTU300 sq ft roomWindow / Wall UnitRecommended Capacity7,000 BTU/hrIllustrative — not to scale. Planning estimate only.

What Is a Window/Portable AC Calculator?

A window/portable AC calculator sizes a standalone room air conditioner — a window, through-the-wall, or portable unit — using Energy Star's official area-to-BTU sizing chart, then adjusts for sun exposure, kitchen use, and occupancy. Unlike whole-house central AC or ductless mini-split sizing (which model an entire home's or multi-room zone's heat gain), this calculator is built specifically for a single, enclosed room served by one self-contained unit.

This calculator is built for homeowners and renters shopping for a room air conditioner. It applies Energy Star's published sizing chart and adjustment factors — it does not replace a full ACCA Manual J load calculation for unusual rooms (very high ceilings, poor insulation, large glazed window walls, or open floor plans), which a licensed HVAC contractor can perform for a precise result.

Why window/wall and portable units get different guidance here:

  • A window or wall unit has a single BTU/hr rating that reflects real delivered cooling reasonably directly — match this calculator's recommendation straight against the unit's nameplate rating
  • A portable unit is dual-rated: an older ASHRAE BTU figure often used in marketing, and a DOE-mandated SACC (Seasonally Adjusted Cooling Capacity) rating that reflects real delivered cooling after accounting for the exhaust hose's infiltration effect — this calculator's recommendation should be matched against SACC, and shows an estimated ASHRAE-label range so you aren't misled by the larger marketed number
  • Both unit types share the same underlying room sizing math (Energy Star's chart plus sun/kitchen/occupancy adjustments) — only the final matching step against the shopping specification differs
  • Large units of either type commonly need a dedicated 230V circuit — this calculator flags that but doesn't size the circuit itself; use the MCA & MOCP Calculator for that separate step

Window/Portable AC Formula: How Is It Determined?

Sizing starts from Energy Star's official area-to-BTU chart, applies three independent adjustments, then rounds up to the next real, purchasable unit size — with an additional SACC/ASHRAE step for portable units only.

Base Capacity from Room Area

Area = Room Length × Room Width, or your entered known area

Base BTU/hr = Energy Star sizing chart lookup for your room's floor area (assumes an 8 ft ceiling)

Energy Star publishes an official chart mapping room floor area directly to a base cooling capacity in BTU/hr, ranging from 5,000 BTU for a 100-150 sq ft room up to 34,000 BTU for a 2,000-2,500 sq ft room. This chart explicitly assumes an 8 ft ceiling — Energy Star gives no official numeric adjustment for taller rooms, only a qualitative note that more capacity may be needed, which this calculator surfaces as a warning rather than an invented multiplier. You can enter a known area directly, or switch Calculation Mode to compute it from the room's length and width instead — both feed the exact same chart lookup.

Sun, Kitchen, and Occupancy Adjustments

Sun adjustment = Base BTU × (+10% very sunny, 0% average, −10% heavily shaded)

Kitchen adjustment = +4,000 BTU flat, if the room is a kitchen

Occupancy adjustment = +600 BTU × occupants beyond a baseline of 2

Adjusted BTU = Base BTU + Sun Adjustment + Kitchen Adjustment + Occupancy Adjustment

These three adjustments come directly from Energy Star's own published sizing guidance, applied on top of the area-based base capacity. Sun exposure and kitchen use both address real, sustained heat gain sources the floor area alone doesn't capture; the occupancy adjustment accounts for body heat from more than the typical 2 people the base chart assumes.

Recommended Nominal Size

Recommended BTU = next available nominal unit size on the sizing chart ≥ Adjusted BTU

The adjusted BTU figure is rounded UP to the next real, purchasable unit size on Energy Star's own chart — never down — since a unit smaller than the actual need runs continuously without ever comfortably reaching the target temperature during peak heat.

Portable Units Only: Estimated ASHRAE-Label Range

Estimated ASHRAE low = Recommended BTU ÷ hose type's maximum SACC/ASHRAE ratio

Estimated ASHRAE high = Recommended BTU ÷ hose type's minimum SACC/ASHRAE ratio

Portable units are dual-rated: SACC (Seasonally Adjusted Cooling Capacity, the DOE-mandated figure reflecting real delivered cooling) and the older ASHRAE BTU figure, which doesn't account for the exhaust hose's infiltration effect and is typically higher. Since SACC is typically 55-71% of ASHRAE for single-hose units and 68-86% for dual-hose units, this calculator shows the estimated ASHRAE-label range you should expect on a unit that actually delivers your recommended real (SACC) capacity — a published estimate range, not a precise per-model conversion, since DOE does not publish one fixed ratio. Always check the specific model's EnergyGuide/DOE label for its actual SACC rating.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValue
Unit typeWindow / Through-the-Wall
Room area300 sq ft
Ceiling height8 ft
Sun exposureAverage / Typical
Kitchen / occupantsNo / 2

Step-by-Step Calculation

StepCalculationResult
Base capacity (300 sq ft)Energy Star chart lookup7,000 BTU/hr
Sun adjustment (Average / Typical)7,000 × 0%+0 BTU/hr
Kitchen adjustmentNot a kitchen+0 BTU/hr
Occupancy adjustment0 extra × 600+0 BTU/hr
Adjusted BTUSum of the above7,000 BTU/hr
Recommended nominal sizeRound up to next chart size7,000 BTU/hr

Therefore, this 300 sq ft room needs a 7,000 BTU/hr window / through-the-wall air conditioner.

Essential Checklist+

Complete these critical checks before approving the work or proceeding to the next construction stage.

7 Inspection Points
4 Verification Categories
Inputs & Sizing Method+
  • Room floor area measured directly (length × width), not estimated or guessed
  • Confirmed the space is a single, enclosed room rather than part of an open floor plan or multi-room area
Unit Type & Rating Selection+
  • Unit type (window/wall vs. portable) matches the room's actual physical constraints, not just personal preference
  • For a portable unit, confirmed checking the model's SACC (Seasonally Adjusted Cooling Capacity) rating on the EnergyGuide/DOE label, not just its marketed ASHRAE BTU number
  • Selected unit's nameplate voltage and amperage checked against the outlet/circuit actually available in the room
Installation Planning+
  • For a window unit, window sill/frame confirmed able to support the unit's weight, with security brackets or a support bracket installed if required
After Installation+
  • Circuit breaker confirmed not tripping under normal startup and running load, especially on shared circuits with other appliances
Full QC Checklist+

Verification checklist for a window/portable air conditioner BTU sizing estimate — covering input/sizing method confirmation, unit type and rating selection, installation planning, and post-installation verification. Use the Essential Checklist for critical checks before finalizing, expand to Full QC Checklist for complete verification.

22 Inspection Points
4 Verification Categories
Inputs & Sizing Method+
  • Room floor area measured directly (length × width), not estimated or guessed
  • Confirmed the space is a single, enclosed room rather than part of an open floor plan or multi-room area
  • Ceiling height confirmed and, if taller than 8 ft, treated as a reason to size up rather than ignored
  • Sun exposure selected honestly for the room's actual orientation and window area, not left at the default
  • Kitchen adjustment applied if the room includes a range, oven, or other major heat-generating appliances
  • Occupant count reflects how many people regularly use the room, not just the default of 2
Unit Type & Rating Selection+
  • Unit type (window/wall vs. portable) matches the room's actual physical constraints, not just personal preference
  • For a portable unit, confirmed checking the model's SACC (Seasonally Adjusted Cooling Capacity) rating on the EnergyGuide/DOE label, not just its marketed ASHRAE BTU number
  • Single-hose vs. dual-hose portable design considered, understanding dual-hose typically delivers a higher share of its ASHRAE rating as real SACC cooling
  • Selected unit's nameplate voltage and amperage checked against the outlet/circuit actually available in the room
  • If the recommended size is large (commonly 18,000 BTU and up), circuit/breaker sizing cross-checked with the MCA & MOCP Calculator against the specific unit's actual nameplate MCA/MOCP
Installation Planning+
  • For a window unit, window sill/frame confirmed able to support the unit's weight, with security brackets or a support bracket installed if required
  • Window/wall unit installation planned with a slight outward tilt (typically 1/4 to 1/2 in low on the outside) so condensate drains away from the building rather than into the room
  • For a portable unit, exhaust hose routed as short and straight as possible to the window/wall port, avoiding sharp bends or excess coiled length
  • Window/slider kit (for a portable unit) or surrounding window frame gaps (for a window unit) sealed with the included foam/weatherstripping
  • Manufacturer-specified clearance around the unit (front intake, side/rear exhaust for window units; front and rear for portable units) confirmed clear of curtains, furniture, or other obstructions
  • In a humid climate, condensate handling plan confirmed for a portable unit — many self-evaporate under moderate humidity but may need a gravity drain hose or internal reservoir emptied under high humidity
After Installation+
  • Cooling performance observed over the first full day of operation, confirming the room reaches and holds its target temperature during peak heat
  • Circuit breaker confirmed not tripping under normal startup and running load, especially on shared circuits with other appliances
  • No unusual rattling, vibration, or excessive noise checked for at both the unit itself and the window frame/wall sleeve
  • Condensate draining outward (window/wall units) or evaporating/collecting as expected (portable units), with no dripping or pooling inside the room
  • For a portable unit, exhaust hose and window kit connection re-checked as secure after the first few days of use, not just at initial installation

Window/Portable AC Reference Tables

Energy Star's official room air conditioner sizing chart, plus the hose-type SACC/ASHRAE ratio ranges used for portable units.

Room AreaBase Capacity
100 to 150 sq ft5,000 BTU/hr
150 to 250 sq ft6,000 BTU/hr
250 to 300 sq ft7,000 BTU/hr
300 to 350 sq ft8,000 BTU/hr
350 to 400 sq ft9,000 BTU/hr
400 to 450 sq ft10,000 BTU/hr
450 to 550 sq ft12,000 BTU/hr
550 to 700 sq ft14,000 BTU/hr
700 to 1000 sq ft18,000 BTU/hr
1000 to 1200 sq ft21,000 BTU/hr
1200 to 1400 sq ft23,000 BTU/hr
1400 to 1500 sq ft24,000 BTU/hr
1500 to 2000 sq ft30,000 BTU/hr
2000 to 2500 sq ft34,000 BTU/hr

Adjustment Factors

ConditionAdjustment
Very sunny room+10% of base capacity
Heavily shaded room−10% of base capacity
Kitchen+4,000 BTU flat
Each occupant beyond 2+600 BTU

Portable AC: Estimated SACC/ASHRAE Ratio by Hose Type

Published estimate ranges only — DOE does not publish one fixed ratio, since it varies by specific model. Always check the EnergyGuide/DOE label for the actual SACC rating.

Hose TypeSACC as % of ASHRAE
Single-Hose55-71%
Dual-Hose68-86%

When should you use this window/portable AC calculator?

  • Shopping for a window, through-the-wall, or portable air conditioner for a single bedroom, living room, home office, or similar enclosed room.
  • Comparing a portable unit's marketed ASHRAE BTU number against what it actually needs to deliver as SACC for your room.
  • Deciding between a single-hose and dual-hose portable unit and understanding how that choice affects the ASHRAE-label figure you should shop for.
  • Checking whether a room's sun exposure, kitchen use, or higher-than-typical occupancy calls for more capacity than the bare floor area alone would suggest.
  • Flagging early whether a larger unit is likely to need a dedicated 230V circuit, before finalizing a purchase.
  • Comparing two scenarios side by side (via Compare mode) — e.g. window vs. portable, or single-hose vs. dual-hose, for the same room.

Quick Sizing Tips

  • For a portable unit, check the EnergyGuide/DOE label for the model's actual SACC rating rather than trusting the larger, marketed ASHRAE BTU figure alone — SACC is the number that reflects what you'll actually feel in the room.
  • Round up to the next available nominal size, never down — a unit smaller than the recommendation runs continuously without properly reaching your target temperature during peak heat.
  • Resist the urge to size up "just in case" beyond this calculator's recommendation — an oversized unit short-cycles, cooling the air quickly but shutting off before it properly removes humidity, leaving the room feeling cold and clammy.
  • If your ceiling is noticeably taller than 8 ft, treat this calculator's recommendation as a floor and consider the next size up, since Energy Star's chart assumes a standard 8 ft ceiling.
  • Prefer a dual-hose portable unit where the price and size difference is acceptable — it typically delivers more of its rated capacity as real SACC cooling than an equivalent single-hose model.
  • Check your lease or building rules before installing a window unit — many buildings require approved support brackets or restrict window units entirely.
  • For any unit in the upper size range, check its nameplate voltage/amperage before buying — some require a dedicated 230V circuit that a standard outlet can't provide.

Common Mistakes

  • Shopping for a portable AC by its marketed ASHRAE BTU number instead of its DOE-mandated SACC rating — the ASHRAE figure can overstate real cooling capacity by 15-45% depending on the model and hose type.
  • Ignoring the sun exposure or kitchen adjustments and sizing purely off floor area — a sunny room or an active kitchen genuinely needs more capacity than the bare area suggests.
  • Using a single room unit to try to cool an open floor plan spanning multiple connected spaces — Energy Star's chart (and this calculator) is built for a single, enclosed room.
  • Buying several sizes larger than the recommendation for "extra cooling power" — oversizing causes short-cycling, which cools quickly but leaves humidity poorly removed.
  • Installing a window unit without a support bracket or a sill rated for its weight, risking the unit falling.
  • Coiling or kinking a portable unit's exhaust hose to make it fit, which increases resistance and reduces real cooling performance below even its rated SACC figure.
  • Ignoring nameplate voltage/amperage on a large unit and discovering only after purchase that it needs an electrical upgrade the room doesn't have.
  • Assuming a taller-than-8-ft ceiling doesn't matter, when Energy Star's own chart is explicitly built around that baseline.

Limitations

  • This is a planning estimate based on Energy Star's published sizing chart and adjustment factors, not a substitute for a full ACCA Manual J room-by-room load calculation, which a licensed HVAC contractor can perform for unusual rooms.
  • Built for a single, enclosed room only — does not model a multi-room open floor plan, which has more effective air volume and heat gain than its combined floor area alone suggests.
  • Energy Star's chart assumes an 8 ft ceiling and gives no official numeric adjustment for taller rooms — this calculator flags the condition qualitatively rather than inventing an unverified per-foot multiplier.
  • The estimated ASHRAE-label range for portable units is a published estimate range (55-71% single-hose, 68-86% dual-hose), not a precise per-model conversion — DOE does not publish one fixed ratio, since it varies by specific model. Always check the EnergyGuide/DOE label for the model's actual SACC rating.
  • Does not size the electrical circuit a large unit needs — use the MCA & MOCP Calculator with the specific model's actual nameplate MCA/MOCP for that separate calculation.
  • Does not account for unusually poor insulation, large glazed window walls, high local humidity beyond typical assumptions, or other above-average heat-gain sources beyond the sun/kitchen/occupancy adjustments modeled here.
  • Beyond the published chart's 2,500 sq ft / 34,000 BTU ceiling, a single room unit is no longer a practical solution — consider a central or ductless multi-zone system instead.
  • Does not verify local building/lease restrictions on window unit installation or replace inspection by a qualified installer.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

Per Energy Star's official sizing chart, a room between 250 and 300 sq ft needs a 7,000 BTU/hr unit as a base figure, before adjustments. That base then gets adjusted ±10% for sun exposure, +4,000 BTU flat if the room is a kitchen, and +600 BTU for each occupant beyond a baseline of 2 — so a very sunny 300 sq ft bedroom for 2 people would round up to an 8,000 BTU unit once the +10% sun adjustment pushes the base above the 7,000 BTU tier.
Window and wall units use a single BTU/hr rating (tested per DOE/CEER standards) that reflects real delivered cooling reasonably well. Portable units are dual-rated: a legacy ASHRAE BTU figure (an idealized test with no infiltration penalty, still often the headline marketing number) and a DOE-mandated SACC — Seasonally Adjusted Cooling Capacity — that accounts for the exhaust hose pulling outdoor heat back into the room. SACC is meaningfully lower than ASHRAE for the same unit, and it's the number that actually reflects what you'll feel in the room.