Well Pump Sizing Calculator (80 ft Lift, Single-Family Example)
Size a well pump for an 80 ft lift with typical fixtures.
🕒 Last updated: August 1, 2026
Pump Scenario & Units
ℹ️Booster boosts an existing pressurized supply; Well/Transfer lifts from an unpressurized well, cistern, or storage tank.
ℹ️Metric converts your entries to/from US units at the boundary — the calculation and result always use US units, matching this site's Drain Pipe Slope calculator.
Required Flow Rate
ℹ️Already know your required flow rate? Enter it directly instead of building a fixture list.
ℹ️Sets which WSFU value applies to each fixture — the same demand engine used on this site's Pipe Sizing by Fixture Units calculator.
ℹ️Flushometer-valve fixtures draw much higher instantaneous flow than flush-tank fixtures at the same fixture-unit count.
Add every fixture this pump needs to serve.
Fixture 1
Fixture 2
Fixture 3
Up to 20 fixture rows total.
Pipe & Head
ℹ️Roughness (Hazen-Williams C = 150, aged/design value) sets how much friction loss this material adds at your flow rate.
ℹ️The pipe size the pump discharges through on its way to the highest/most remote fixture.
ℹ️Full developed length from the pump to the highest/most remote fixture, including vertical runs.
ℹ️Full vertical lift from your well/cistern/tank water level up to your highest fixture.
ℹ️Pressure you want left over at the highest/most remote fixture — IPC code minimums are 8-15 psi, but 20-30+ psi is a more comfortable design target.
Pump Efficiency
ℹ️Defaults to 65%, typical for a small centrifugal pump — adjust to a specific candidate pump's published efficiency at your duty point if known.
Optionally size a hydropneumatic pressure tank's drawdown alongside the pump.
Optionally estimate the pump's electricity cost from your own rate and daily run time.
🔧 Required: 9.9 GPM at 161.92 ft TDH
Scenario: Well / Transfer Pump
Flow Rate
Water Closet (1.6 GPF, Gravity Tank) (x3): 2.5 WSFU
Shower (x2): 1.5 WSFU
Lavatory (x3): 0.8 WSFU
Required Flow Rate: 9.9 GPM
Total Dynamic Head Breakdown
Elevation: 80 ft
Friction Loss: 12.62 ft
8.41 ft per 100 ft of 1" pipe
Required Pressure Head: 69.3 ft (30 psi)
Total Dynamic Head: 161.92 ft
Pump Power & Motor Class
Water HP: 0.405 HP
Brake HP (Efficiency 65%): 0.623 HP
Motor-Size Class: 3/4 HP class
Pump configuration: Single unit, or duplex for standby redundancy
Design Notes
Friction loss is computed directly from your pipe material, size, and run length via the Hazen-Williams equation — using conservative, aged-condition roughness values rather than optimistic new-pipe numbers.
A Well/Transfer Pump always needs to create its full head from scratch — there's no existing pressurized supply to credit against, unlike a Booster scenario.
Always confirm a shortlisted pump's actual published pump curve at this required GPM/TDH duty point — a horsepower label alone doesn't guarantee a specific pump meets this exact operating point.
Approximate results for planning only. Verify with a professional.
Looking for the verification checklist, reference tables, or tips and mistakes?See the complete Water Pump / Pressure Booster Sizing Calculator.
80 ft lift well pump sizing example
The same 12.9 WSFU fixture load (9.9 GPM) as a typical single-family home, but a Well/Transfer scenario gets no credit for existing pressure — the pump must create the entire 80 ft lift, 12.62 ft of friction loss through 150 ft of 1" PEX, and a 30 psi (69.3 ft) required residual pressure from scratch.
That totals 161.92 ft of TDH, needing approximately 0.623 BHP — rounding up to a 3/4 HP motor class with a comfortable 20.4% margin.
- 9.9 GPM required flow rate — the pump creates 100% of the head, no incoming-pressure credit.
- 161.92 ft TDH (80 ft lift + 12.62 ft friction + 69.3 ft pressure head).
- ≈0.623 BHP → 3/4 HP motor class.
How Water Pump Sizing Is Calculated
The calculation runs in six parts — friction loss, Total Dynamic Head, pump power, motor-size class, and (optionally) pressure tank sizing and operating cost.
Step 1 — Friction Loss (Hazen-Williams)
C is the Hazen-Williams roughness coefficient for your selected pipe material (Copper 130, Galvanized Steel 100, CPVC/PEX 150 — conservative "aged pipe" design values), Q is your required flow rate in GPM, and d is the selected nominal size's actual inner diameter in inches. The result scales directly with your pipe run length.
Step 2 — Total Dynamic Head (TDH)
Well/Transfer: TDH = Elevation + Friction Loss + Required Pressure × 2.31
2.31 converts psi to feet of head (1 psi = 2.31 ft, from water's density). For a Booster scenario, if the available incoming pressure already covers the requirement once elevation and friction are subtracted, TDH comes out to zero or less — this calculator reports "pump not needed" rather than sizing one anyway. A Well/Transfer scenario always needs a pump, since there's no existing pressurized supply to credit against.
Step 3 — Pump Power
Brake HP = Water HP ÷ Efficiency
Water Horsepower is the theoretical minimum power for a perfect, lossless pump; Brake Horsepower divides that by your pump's actual efficiency (default 65%, typical for a small centrifugal pump) to get the real shaft power the motor must supply.
Step 4 — Motor-Size Class & Feasibility
Margin % = (Motor Class − Brake HP) ÷ Brake HP × 100
Brake Horsepower is matched against standard NEMA fractional/whole HP steps (1/3 through 20 HP) to show what to actually shop for, classified as comfortable (15-50% headroom), borderline (under 15%), or oversized(over 50%). A requirement beyond 20 HP triggers a feasibility warning and a dual-unit (parallel pumps) check rather than an extrapolated guess. A discharge-pressure check also flags if the pump would push a nearby fixture above IPC 604.8's 80 psi maximum.
Step 5 — Pressure Tank Sizing (Optional)
Size a Tank: Required Tank Volume (gal) = (Flow Rate × Run Time) ÷ (P1 ÷ P2 − P1 ÷ P3)
Both directions use Boyle's Law, where P1 = precharge, P2 = cut-in, P3 = cut-out — all three converted to absolute pressure(gauge psi + 14.7) before the ratio. "Check a Tank" tells you the drawdown a candidate tank volume delivers; "Size a Tank" solves the same equation in reverse, turning a target minimum pump run time into the minimum tank volume needed, rounded up to the nearest common standard size. Skip this step by leaving Pressure Tank Sizing on "Skip" if you only need the pump sized.
Step 6 — Operating Cost (Optional)
Daily Cost = Electrical kW × Hours per Day × Electricity Rate
Brake HP is shaft power, not electrical input power — a motor's own electrical-to-mechanical conversion is never 100%, so dividing by Motor Efficiency (default 85%, adjustable) converts shaft power to the actual power drawn at the wall. Hours per day is always a value you enter directly, never guessed from other inputs — actual daily pump run time varies too much by household and system to safely infer. Monthly and annual figures simply multiply the daily cost by 30 and 365 respectively, at the same constant daily usage.
Worked Example
This example uses the active inputs above and follows the same steps as the Formula section.
Input Values Used
| Input | Value |
|---|---|
| Pump Scenario | Well / Transfer Pump (From Well, Cistern, or Tank) |
| Required Flow Rate | Water Closet (1.6 GPF, Gravity Tank) x3, Shower x2, Lavatory x3 |
| Pipe | PEX (CTS), 1", 150 ft run |
| Elevation / Required Pressure | 80 ft / 30 psi |
Step 1 — Friction Loss
| Calculation | Substitution | Result |
|---|---|---|
| Friction Loss (per 100 ft) | C=150, Q=9.9 GPM, d=0.959 in | 8.41 ft/100ft |
| Friction Loss (full run) | 8.41 × (150 ÷ 100) | 12.62 ft |
Step 2 — Total Dynamic Head
| Calculation | Substitution | Result |
|---|---|---|
| Required Pressure Head | 30 psi × 2.31 | 69.3 ft |
| Total Dynamic Head | 80 + 12.62 + 69.3 | 161.92 ft |
Step 3 — Pump Power & Motor Class
| Calculation | Substitution | Result |
|---|---|---|
| Water HP | (9.9 × 161.92) ÷ 3960 | 0.405 HP |
| Brake HP | 0.405 ÷ 0.65 | 0.623 HP |
| Motor-Size Class | Nearest standard class ≥ 0.623 HP | 3/4 HP (comfortable) |
Therefore, this scenario needs a pump rated for at least 9.9 GPM at 161.92 ft of TDH — approximately 0.623 HP brake horsepower, closest to a 3/4 HP standard motor class (comfortable).
This does not cover suction-side sizing, NPSH, or electrical service. Cross-check against the Reference Tables in the complete Water Pump / Pressure Booster Sizing Calculator.
This page keeps things focused on the calculation above. For the full construction guide — verification checklist, reference tables, usage steps, tips, common mistakes, and limitations.See the complete Water Pump / Pressure Booster Sizing Calculator.