TryBuildCalc

Room-by-Room CFM Calculator (Proportional Load-Based Allocation)

Allocate CFM to your rooms instantly.

Inputs

Calculation Mode

System Design Data

Use the selected equipment's actual design airflow, and room/system loads from one consistent load calculation.

Seasons Served
CFM
BTU/hr
CFM
BTU/hr

Room Loads

Add every room, or only the ones you want to check.

Room 1

BTU/hr
BTU/hr

Room 2

BTU/hr
BTU/hr

Room 3

BTU/hr
BTU/hr

Room 4

BTU/hr
BTU/hr

System Design Airflow

1,200 CFM

Room-by-Room Allocation

Cooling System Airflow

1,200 CFM

Heating System Airflow

1,000 CFM

RoomCooling CFMHeating CFMDesign CFMGoverning
Living Room360200360Cooling
Primary Bedroom240300300Heating
Bedroom 2240250250Heating
Kitchen / Dining360250360Cooling

Room CFM values are apportioned so this table's column totals always match the assigned airflow below, even when an individual room's exact share isn't a whole number.

AIR HANDLER1,200 CFMLiving Room360 CFM · CoolingPrimary Bedroom300 CFM · HeatingBedroom 2250 CFM · HeatingKitchen / Dining360 CFM · CoolingIllustrative airflow path; duct and outlet sizing require separate design checks.

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete HVAC Airflow / Room CFM Calculator.

Room-by-room CFM allocation

Once you know a system's actual design airflow, each room's target CFM is that system airflow multiplied by the room's own share of the whole-system load — cooling airflow follows cooling load share, heating airflow follows heating load share, independently.

This page defaults to a 4-room, 1,200/1,000 CFM cooling/heating system — edit the inputs above to match your own load calculation and equipment.

HVAC Airflow Formulas

Each mode uses its own independent formula — pick the one that matches what you already know, not the one that seems simplest.

Sensible Load to CFM

CFM = Sensible Load (BTU/hr) ÷ (1.08 × ΔT °F)

ΔT = absolute supply-to-room temperature difference

The 1.08 factor is standard air's specific heat capacity per unit volume per hour (60 min/hr × 0.075 lb/ft³ standard air density × 0.24 BTU/lb·°F) — a textbook ACCA/ASHRAE relationship, not a rule of thumb. It assumes standard air density and does not self-correct for altitude or unusual conditions. Use sensible load only; the equation has no term for latent (moisture-removal) heat. The displayed CFM is rounded up, never to nearest, so it never understates the calculated requirement.

Equipment Capacity to CFM

Target CFM = Cooling Tons × Selected CFM/ton

Safe planning band = Tons × 350 to 450 CFM/ton

400 CFM/ton is ACCA's own cited baseline, balancing sensible and latent capacity at standard conditions (80°F/50% RH). The 350–450 CFM/ton band is bounded by real coil failure modes, not an arbitrary range: below it, the coil risks icing; above it, condensed moisture risks blowing off the coil before it drains. This is a preliminary planning target — the matched equipment's own blower performance table at its actual installed external static pressure governs the final airflow.

Room-by-Room Allocation

Cooling Factor = System Cooling CFM ÷ Total Cooling Sensible Load

Room Cooling CFM = Cooling Factor × Room Cooling Sensible Load

Heating Factor = System Heating CFM ÷ Total Heating Load

Room Heating CFM = Heating Factor × Room Heating Load

Room Design CFM = larger of Room Cooling CFM or Room Heating CFM

This is a proportional split of a known system airflow — not an independent calculation of what each room needs on its own. Room and total loads must come from the same load calculation, or the resulting percentages don't represent anything real. The larger of the two seasonal values becomes each room's branch target, since the same duct and register have to serve both seasons.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValue
System cooling / heating airflow1,200 / 1,000 CFM
Total cooling / heating load24,000 / 30,000 BTU/hr
Living Room cooling / heating load7,200 / 6,000 BTU/hr

Step-by-Step Calculation

StepCalculationResult
Cooling factor1,200 ÷ 24,0000.05 CFM/BTU·hr
Heating factor1,000 ÷ 30,0000.03333 CFM/BTU·hr
Living Room cooling CFM (exact, before apportionment)7,200 × 0.05360 CFM
Living Room heating CFM (exact, before apportionment)6,000 × 0.03333200 CFM
Living Room design CFM (governing)max(360, 200)360 CFM (Cooling)

Room CFM values are apportioned (using a largest-remainder method) so the whole-number values in the room table always sum to the assigned CFM total shown above — a single room's exact share, before that adjustment, can differ from the table by a fraction of a CFM.

Therefore, Living Room needs 360 CFM (Cooling), out of a system total of 1,200 CFM.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

Cooling and heating loads for the same room are rarely identical (a north-facing bedroom might need more heating than cooling, for example), so the proportional split is computed independently for each season. The room's final design CFM is whichever of the two is larger.
Not necessarily for a partial check, but for a complete design, yes — every CFM the equipment moves needs a place to go. This calculator flags any unallocated airflow so it isn't silently lost from the design.