TryBuildCalc

Concrete-Encased Electrode GEC Size Calculator (Ufer Ground — NEC 250.66(B))

Size the GEC to a Ufer ground.

Inputs

ℹ️Governs both the largest-ungrounded-conductor column and the resulting GEC size — Table 250.66 uses genuinely different size boundaries for copper and aluminum.

ℹ️The largest ungrounded (phase) conductor at the service, feeder, or separately derived system — check the panel schedule or as-built drawings. For parallel conductor sets, use the total equivalent area.

ℹ️A rod/pipe/plate electrode caps the GEC at 6 AWG copper or 4 AWG aluminum (NEC 250.66(A)); a concrete-encased electrode caps it at 4 AWG copper (NEC 250.66(B)) — both only when it's the sole connection. A ground ring instead matches its own conductor size, per 250.66(C).

Cost

Enable Cost Estimation?

Required Grounding Electrode Conductor: 4 AWG (Copper)

Sized directly from NEC Table 250.66, no electrode-type cap applies

NEC Table 250.66 Lookup

Largest ungrounded conductor: 3/0 AWG

Table row: 2/0 or 3/0 AWG (Cu) / 4/0 AWG or 250 kcmil (Al)

Table-derived GEC size: 4 AWG

Electrode Type Check

Electrode type: Concrete-encased electrode / Ufer ground (sole connection)

No electrode-specific cap applies — the table size governs

Assumptions Used

NEC Table 250.66 (grounding electrode conductor size for AC systems), NEC 250.66(A)/(B)/(C) electrode-specific caps, NEC 250.64(A) aluminum earth-contact restriction. Assumes a single, homogeneous conductor material for both the ungrounded conductor and the GEC. This is a reference estimate — confirm against the code edition adopted in your jurisdiction and a licensed electrician before final installation.

Want the full walkthrough on Table 250.66, the electrode-specific caps, and connector types? Grounding Electrode Conductor Sizing Guide →

Grounding Electrode ConductorPanel4 AWGConcrete-encased electrode / Ufer groundDiagram simplified for clarity (not to scale)

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Grounding Electrode Conductor Size Calculator.

Concrete-encased electrode (Ufer ground) GEC sizing

A concrete-encased electrode — commonly called a Ufer ground — is typically rebar or a bare copper conductor encased in at least 2 inches of concrete at the base of a footing or foundation, in direct contact with the earth. It's a highly effective, low-resistance electrode in most soil conditions.

This page is pre-set to a 3/0 AWG copper largest ungrounded conductor with the concrete-encased electrode type selected — edit the inputs above to match your actual service.

  • The 4 AWG copper cap applies to the portion of the conductor that is the sole connection to the concrete-encased electrode.
  • New construction commonly requires a concrete-encased electrode where the qualifying conditions of NEC 250.52(A)(3) are met.
  • Connections that will be encased in the concrete pour need an exothermic weld or a connector specifically listed for direct concrete encasement, per NEC 250.68(A).

Grounding Electrode Conductor Formula: How Is the Size Determined?

Two steps: a direct NEC Table 250.66 lookup, then an electrode-specific cap check.

Step 1 — Table 250.66 Lookup

Convert Largest Ungrounded Conductor Size to circular mils (AWG table lookup, or kcmil x 1000)

Find the Table 250.66 row whose range contains that value, for the selected material (Cu or Al)

Table GEC Size = that row's GEC size, in the same material

Table 250.66 has 7 rows, each covering a range of largest-ungrounded-conductor sizes, with separate copper and aluminum/copper-clad aluminum columns — the two materials have genuinely different range boundaries, not a scaled version of each other.

Step 2 — Electrode-Type Cap

Rod/pipe/plate (sole connection): Final GEC = the SMALLER of Table GEC Size and 6 AWG copper / 4 AWG aluminum (NEC 250.66(A))

Concrete-encased electrode (sole connection): Final GEC = the SMALLER of Table GEC Size and 4 AWG copper (NEC 250.66(B)) — copper only, no aluminum cap is published

Ground ring (sole connection): GEC matches the ring's own conductor, minimum 2 AWG copper (NEC 250.66(C))

Other/multiple electrodes: Final GEC = Table GEC Size, no cap applied

These caps only apply to the portion of the conductor that is the SOLE connection to that specific electrode type — a conductor that also serves another purpose is not automatically capped the same way. Aluminum GEC directly connected to a rod/pipe/plate, concrete-encased, or ground-ring electrode is flagged separately, since NEC 250.64(A) restricts aluminum from direct earth/masonry contact regardless of the size cap.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Largest ungrounded conductor3/0 AWG, copperSets the Table 250.66 row and material column
Electrode typeConcrete-encased electrode / Ufer ground (sole connection)Determines which electrode-specific cap, if any, applies

Step 1 — Table 250.66 Lookup

CalculationResult
Table row2/0 or 3/0 AWG (Cu) / 4/0 AWG or 250 kcmil (Al)
Table-derived GEC size4 AWG

Step 2 — Electrode-Type Cap

CalculationResult
Cap checkNo electrode-specific cap applies
Final recommended size4 AWG (copper)

Therefore, for a 3/0 AWG copper largest ungrounded conductor connecting to concrete-encased electrode / ufer ground (sole connection), you need approximately 4 AWG copper for the grounding electrode conductor.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

NEC 250.66(B) caps it at 4 AWG copper for the same reason as the rod/pipe/plate cap — a concrete-encased electrode is already a highly effective, low-resistance connection to earth, so a larger conductor beyond this size doesn't meaningfully improve it.
Where the connection point will itself be encased in concrete and inaccessible after the pour, NEC 250.68(A) requires an exothermic weld or a connector specifically listed for that purpose — an ordinary mechanical clamp is not sufficient there.