Branch Duct Size Calculator (Single-Room Branch Sizing)

Size your branch duct instantly.

Inputs

tons

ℹ️Used only for the Suggested Total System CFM cross-check — never auto-applied to any run's own CFM.

ℹ️350 CFM/ton for humid climates, 400 standard, 450 for dry climates — used with tonnage for the cross-check above.

Duct Runs

Run 1
CFM

Duct Runs Sized

1

run

Suggested Total System CFM

Not entered

Enter system tonnage above for a cross-check reference

Simplified velocity-based sizing — not a Manual D duct design. This calculator sizes duct diameter using a simplified velocity-only method — its velocity targets are common planning limits informed by ACCA Manual D guidance, not the full Manual D equal-friction duct-sizing procedure, which sizes ducts from design airflow, friction rate, duct material/roughness, and total system static pressure. It does not account for duct length, fitting/elbow friction loss, total effective length, or your system's available static pressure budget. Get a full Manual D duct design from a licensed HVAC contractor before fabrication or installation.

Bedroom Branch

Supply Branch150 CFM

7 in Round Duct

Target 600 FPM (max 700 FPM) — actual velocity at 7 in is 561 FPM

Duct Size Estimate1 duct run sized by velocityAir handlerBedroom BranchBedroom Branch7 inIllustrative — not to scale. Simplified velocity-only sizing, not a Manual D design.

Looking for the verification checklist, reference tables, tips, or common mistakes?See the complete Duct Size Calculator.

Branch duct sizing

A branch run carries one room's share of the total system airflow off the trunk — since branches serve occupied rooms directly, they target a slower recommended velocity (600 FPM) than a trunk, for quieter operation.

This page defaults to a 150 CFM branch (a typical single-bedroom share) — edit the CFM above to match that room's actual load.

Duct Size Calculator Formula: How Is It Determined?

Each run is sized independently from its own CFM and duct category, then rounded up to a standard stock size.

Step 1 — Required Area at Target Velocity

Required Area (sq ft) = Run CFM ÷ Target Velocity (FPM)

Target velocity is the selected duct category's recommended (not maximum) planning limit, informed by common ACCA Manual D velocity guidance — Supply Trunk 700 FPM, Supply Branch 600 FPM, Return Trunk 600 FPM, Return Branch 400 FPM. This is a velocity-only shortcut, not the full Manual D method, which also uses design airflow, friction rate, duct properties, and total system resistance.

Step 2 — Raw Diameter

Raw Diameter (in) = √(4 x Required Area ÷ π) x 12

This converts the required round cross-sectional area into an exact diameter in inches — before rounding to a stock size.

Step 3 — Nominal Size & Actual Velocity

Nominal Diameter = next standard size ≥ Raw Diameter, up to 24 in

Actual Velocity = Run CFM ÷ Area(Nominal Diameter)

The raw diameter always rounds UP to the next standard round duct size (4 through 24 in) — sizing down would run faster than the target velocity. The actual velocity at that standard size is shown for transparency, and is usually a little under the target since sizes snap up in whole-inch steps. A run whose raw diameter exceeds 24 in is flagged, not capped.

Worked Example

This example walks through your current inputs above, using the same steps as the Formula section.

Input Values Used

InputValueWhy it is used
Run count1Each run is sized independently below
Suggested total system CFMNot enteredInformational cross-check only, not applied to any run

Step 1 — Required Area per Run

Required area = run CFM ÷ that duct category's target velocity.

RunCalculationRaw Diameter
Bedroom Branch (Supply Branch)150 CFM ÷ 600 FPM6.77 in

Step 2 — Nominal Size & Actual Velocity

RunRaw DiameterNominal SizeActual Velocity
Bedroom Branch6.77 in7 in561 FPM

Therefore, this 1-run duct system sizes to the standard diameters shown above, each achieving a velocity at or under its category's recommended target. This is a simplified velocity-based sizing shortcut — get a full Manual D design from a licensed HVAC contractor before fabrication or installation.

Disclaimer: This calculator provides approximate results for planning and estimation purposes only. Actual requirements may vary based on site conditions, materials, workmanship, and local building regulations. Always consult a qualified engineer, architect, or construction professional before making final decisions.

FAQ

That room's own share of total system CFM, ideally from a room-by-room Manual J load calculation — a rough rule of thumb is total system CFM divided by number of rooms, but actual room loads vary.
A branch carries only one room's airflow share, while the trunk carries the combined airflow for every room it feeds — lower CFM alone would size it smaller, and the slower branch velocity target narrows the gap only slightly.